GE Multilin
L90 Line Current Differential System
10-27
10 APPLICATION OF SETTINGS
10.9 PHASE DISTANCE THROUGH POWER TRANSFORMERS
10
10.9PHASE DISTANCE THROUGH POWER TRANSFORMERS
10.9.1 PHASE DISTANCE PROTECTION
a) DESCRIPTION
Phase distance elements of the L90 could be set to respond to faults beyond any three-phase power transformer. The relay
guarantees accurate reach and targeting for any phase fault. Moreover, the current and voltage transformers may be
located independently on different sides of the transformer.
The following setting rules apply to this feature:
1.
A given distance zone is terminated by location of the VTs, not the CTs.
2.
Consequently, the positive-sequence impedance of a transformer must be included in the reach setting only if the
transformer is located between the potential source and the intended reach point.
3.
The current signals require compensation if the transformer is located between the CTs and the intended reach point.
If this is the case the CT connection setting shall be set to transformer connection and vector group as seen from the
CTs toward the reach point. Otherwise, the CT connection setting shall be set to "None".
4.
The voltage signals require compensation if the transformer is located between the VTs and the intended reach point.
If this is the case the VT connection setting shall be set to transformer connection and vector group as seen from the
VTs toward the reach point. Otherwise, the VT connection setting shall be set to "None".
5.
The reach setting is entered in secondary ohms and as such must take into account location and ratios of VTs and CTs
as well as voltage ratio of the involved power transformer.
The following equations explain the setting rules. Consider two applications as shown in the figure below:
PHASE DISTANCE LOOKING THROUGH A POWER TRANSFORMER
where:Z
X
= intended reach impedance for Zone 1
(primary ohms)
Z
H
= intended reach impedance for (primary ohms)
Z
T
= positive-sequence impedance of the transformer
V
X
, V
H
= transformer rated voltages
n
CT
= transformation ratio of the CTs
n
VT
= transformation ratio of the VTs
Z1: Z1 reach setting (secondary ohms)
: Zone reach setting (secondary ohms)
b) ZONE 1 SETTING IN APPLICATION (A)
As the transformer is located between the potential source and the reach point for Zone 1, the reach impedance must
include the positive-sequence impedance of the transformer. In addition, the primary impedance must be re-calculated for
the voltage level of the VTs and CTs, and eventually, re-calculated to secondary quantities:
(EQ 10.21)
c) ZONE 4 SETTING IN APPLICATION (A)
As the transformer is not located between the potential source and the reach point for , the reach impedance must not
include the positive-sequence impedance of the transformer. Because both VTs and CTs are located on the same side as
the intended reach point, no correction for the transformer ratio is required. The primary impedance must be only re-calcu-
lated to secondary quantities:
X
H
Z
X
Z1
Z
H
Z
T
Z4
(a)
X
H
Z
X
Z1
Z
H
Z
T
Z4
(
b
)
Z
1
Z
T
at X
Z
x
V
H
V
X
-------
2
n
CT
n
VT
---------
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...