5-278
L90 Line Current Differential System
GE Multilin
5.7 CONTROL ELEMENTS
5 SETTINGS
5
THREE VT BREAKER FLASHOVER APPLICATION
When only one set of VTs is available across the breaker, the
BRK 1 FLSHOVR SIDE 2 SRC
setting should be “None”. To detect
an open breaker condition in this application, the scheme checks if the per-phase voltages were recovered (picked up), the
status of the breaker is open (contact input indicating the breaker status is off), and no flashover current is flowing. A con-
tact showing the breaker status must be provided to the relay. The voltage difference will not be considered as a condition
for open breaker in this part of the logic.
Voltages must be present prior to flashover conditions. If the three VTs are placed after the breaker on the line (or
feeder), and the downstream breaker is open, the measured voltage would be zero and the flashover element will
not be initiated.
The flashover detection will reset if the current drops back to zero, the breaker closes, or the selected FlexLogic operand
for supervision changes to high. Using supervision through the
BRK 1 FLSHOVR SPV A
,
BRK 1 FLSHOVR SPV B
, and
BRK 1
FLSHOVR SPV C
settings is recommended by selecting a trip operand that will not allow the flashover element to pickup prior
to the trip.
The flashover detection can be used for external alarm, re-tripping the breaker, or energizing the lockout relay.
Consider the following configuration:
The source 1 (SRC1) phase currents are feeder CTs and phase voltages are bus VTs, and Contact Input 1 is set as Breaker
52a contact. The conditions prior to flashover detection are:
1.
52a status = 0.
2.
VAg, VBg, or VCg is greater than the pickup setting.
3.
IA, IB, IC = 0; no current flows through the breaker.
4.
VA is greater than pickup (not applicable in this scheme).
The conditions at flashover detection are:
1.
52a status = 0.
2.
IA, IB, or IC is greater than the pickup current flowing through the breaker.
3.
VA is greater than pickup (not applicable in this scheme).
SIX VT BREAKER FLASHOVER APPLICATION
The per-phase voltage difference approaches zero when the breaker is closed. The is well below any typical minimum
pickup voltage. Select the level of the
BRK 1 FLSHOVR DIFF V PKP
setting to be less than the voltage difference measured
across the breaker when the close or open breaker resistors are left in service. Prior to flashover, the voltage difference is
larger than
BRK 1 FLSHOVR DIFF V PKP
. This applies to either the difference between two live voltages per phase or when the
voltage from one side of the breaker has dropped to zero (line de-energized), at least one per-phase voltage is larger than
the
BRK 1 FLSHOVR V PKP
setting, and no current flows through the breaker poles. During breaker flashover, the per-phase
voltages from both sides of the breaker drops below the pickup value defined by the
BRK 1 FLSHOVR V PKP
setting, the volt-
age difference drops below the pickup setting, and flashover current is detected. These flashover conditions initiate Flex-
Logic pickup operands and start the
BRK 1 FLSHOVR PKP DELAY
timer.
This application do not require detection of breaker status via a 52a contact, as it uses a voltage difference larger than the
BRK 1 FLSHOVR DIFF V PKP
setting. However, monitoring the breaker contact will ensure scheme stability.
NOTE
842746A1.CDR
Bus VTs
Line/Feeder
Breaker
CTs
Bus
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...