GE Multilin
L90 Line Current Differential System
9-27
9 THEORY OF OPERATION
9.3 DISTANCE ELEMENTS
9
Left Blinder RCA: 88°
Polarizing Current: Zero-sequence
Non-Homogeneity Correction Angle: 3°
Directional RCA: 88°
Z0/Z1 Magnitude: 4.55
Overcurrent supervision: 3 A
Z0/Z1 Angle: –12°
Distance Comparator limit angle: 75°
Z0M/Z1 Magnitude: 0
Directional Comparator limit angle: 75°
Assume the following signals are injected to the relay:
V
A
= 64.71 V
0.0° (pre-fault)
V
A
= 25.43 V
–19.9°
V
B
= 80.22 V
–133.5°
V
C
= 77.33 V
135.7°
I
A
= 4.47 A
–107.8°
I
B
= 2.92 A
68.9°
I
C
= 2.93 A
–51.1°
Based on the entered setting the relay calculates:
K0 = 3.58
–15.2°
K0M= 0
Z
= 14.00
88°
Z
D
= 1
88°
Z
R
= 9.99
2°
Z
L
= 4.99
178°
For the assumed steady-state injection the relay calculates:
V
A
_1
= 58.83 V
–2.1°
V
A
_1M
= 64.71 V
0.0°
I_0
= 1.37 A
–68.2°
I
A
_2
= 1.37 A
–68.1°
–V_0
= 29.18 V
8.4°
(V
A
–V
B
)_1
= 93.35 V
32.0°
(V
A
–V
B
)_1M
= 112.08 V
30.0°
I
A
–I
B
= 7.39 A
–109.1°
b) MHO PHASE A TO GROUND ELEMENT (BEFORE MEMORY EXPIRES)
I
A
Z + I_0
K0
Z + I
A
K0M
Z – V
A
= 103.33 V
–3.9°
V
A
_1M =
64.71
V
0.0°
I
A
_2
Z
D
=
1.37
V
19.8°
I_0
Z =
19.11
V
19.8°
I_0
Z
D
= 1.37 V
19.8°
•
Overcurrent supervision: | 3
I_0 | = 4.09 A
3 A
•
Mho difference angle = | –3.9° – 0° | = 3.9°
75°
•
Reactance difference angle = | –3.9° – 19.8° | = 23.7°
75°
•
Zero-sequence directional difference angle = | 19.8° – 0.0° | = 19.8°
75°
•
Negative-sequence directional difference angle = | 19.8° – 0.0° | = 19.8°
75°
•
Fault-type comparator difference angle = | 19.8° – 19.8° | = 0.0°
50°
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...