5 SETTINGS
5.6 GROUPED ELEMENTS
5
The positive-sequence restraint must be considered when testing for pick-up accuracy and response time (multiple of
pickup). The positive-sequence restraint is removed for low currents. If the positive-sequence current is less than 0.8 pu,
then the restraint is removed by changing the constant
K
to zero. This results in better response to high-resistance faults
when the unbalance is very small and there is no danger of excessive CT errors, since the current is low.
The
operating quantity
depends on the way the test currents are injected into the L90. For single phase injection:
•
I
op
=
⅓
(1 –
K
I
injected
for I_2 mode.
•
I
op
= (1 –
K
I
injected
for I_0 mode if I_1 > 0.8 pu.
The
directional unit
uses the negative-sequence current (I_2) and negative-sequence voltage (V_2).
The following tables define the negative-sequence directional overcurrent element.
Table 5–26: NEGATIVE-SEQUENCE DIRECTIONAL OVERCURRENT UNIT
Table 5–27: NEGATIVE-SEQUENCE DIRECTIONAL UNIT
The negative-sequence voltage must be greater than 0.02 pu to be validated for use as a polarizing signal. If the polarizing
signal is not validated neither forward nor reverse indication is given. The following figure explains the usage of the voltage
polarized directional unit of the element.
The figure below shows the phase angle comparator characteristics for a phase A to ground fault, with settings of:
ECA
= 75° (element characteristic angle = centerline of operating characteristic)
FWD LA = 80° (forward limit angle = ± the angular limit with the ECA for operation)
REV LA
= 80° (reverse limit angle = ± the angular limit with the ECA for operation)
MODE
OPERATING CURRENT
Negative-sequence
I
op
= |I_2| –
K
I_1|
Zero-sequence
I
op
= 3 × (|I_0| –
K
× |I_1|) if |I_1| > 0.8 pu
I
op
= 3 × |I_0| if |I_1|
≤
0.8 pu
DIRECTION
COMPARED PHASORS
Forward
–V_2
Z_offset
I_2
I_2
1
ECA
Reverse
–V_2
Z_offset
I_2
–(I_2
1
ECA)
Forward
–V_2
Z_offset
I_2
I_2
1
ECA
Reverse
–V_2
Z_offset
I_2
–(I_2
1
ECA)
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...