GE Multilin
L90 Line Current Differential System
5-137
5 SETTINGS
5.5 FLEXLOGIC
5
ELEMENT:
Underfrequency
UNDERFREQ 1 PKP
UNDERFREQ 1 OP
UNDERFREQ 1 DPO
Underfrequency 1 has picked up
Underfrequency 1 has operated
Underfrequency 1 has dropped out
UNDERFREQ 2 to 6
Same set of operands as shown for UNDERFREQ 1 above
ELEMENT:
Wattmetric zero-
sequence
directional
WATTMETRIC 1 PKP
WATTMETRIC 1 OP
Wattmetric directional element 1 has picked up
Wattmetric directional element 1 has operated
WATTMETRIC 2...
Same set of operands as per WATTMETRIC 1 above
FIXED OPERANDS
Off
Logic = 0. Does nothing and may be used as a delimiter in an equation list;
used as ‘Disable’ by other features.
On
Logic = 1. Can be used as a test setting.
INPUTS/OUTPUTS:
Contact inputs
Cont Ip 1
On
Cont Ip 2
On
Cont Ip 1
Off
Cont Ip 2
Off
(will not appear unless ordered)
(will not appear unless ordered)
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
current
(from detector on
form-A output only)
Cont Op 1 IOn
Cont Op 2 IOn
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS:
Contact outputs,
voltage
(from detector on
form-A output only)
Cont Op 1 VOn
Cont Op 2 VOn
(will not appear unless ordered)
(will not appear unless ordered)
Cont Op 1 VOff
Cont Op 2 VOff
(will not appear unless ordered)
(will not appear unless ordered)
INPUTS/OUTPUTS:
Direct input
Direct I/P 1-1 On
Direct I/P 1-8 On
(appears only when an inter-relay communications card is used)
(appears only when inter-relay communications card is used)
Direct I/P 2-1 On
Direct I/P 2-8 On
(appears only when inter-relay communications card is used)
(appears only when inter-relay communications card is used)
INPUTS/OUTPUTS:
Remote double-
point status inputs
RemDPS Ip 1 BAD
RemDPS Ip 1 INTERM
RemDPS Ip 1 OFF
RemDPS Ip 1 ON
Asserted while the remote double-point status input is in the bad state.
Asserted while the remote double-point status input is in the intermediate
state.
Asserted while the remote double-point status input is off.
Asserted while the remote double-point status input is on.
REMDPS Ip 2...
Same set of operands as per REMDPS 1 above
INPUTS/OUTPUTS:
Remote inputs
REMOTE INPUT 1 On
REMOTE INPUT 2 On
REMOTE INPUT 2 On
REMOTE INPUT 32 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual inputs
Virt Ip 1
On
Virt Ip 2
On
Virt Ip 3
On
Virt Ip 64
On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
INPUTS/OUTPUTS:
Virtual outputs
Virt Op 1 On
Virt Op 2 On
Virt Op 3 On
Virt Op 96 On
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Table 5–12: L90 FLEXLOGIC OPERANDS (Sheet 9 of 11)
OPERAND TYPE
OPERAND SYNTAX
OPERAND DESCRIPTION
Содержание UR Series L90
Страница 14: ...xiv L90 Line Current Differential System GE Multilin 0 1 BATTERY DISPOSAL 0 BATTERY DISPOSAL 0 ...
Страница 68: ...2 34 L90 Line Current Differential System GE Multilin 2 4 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2 ...
Страница 138: ...4 30 L90 Line Current Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 604: ...9 58 L90 Line Current Differential System GE Multilin 9 6 FAULT LOCATOR 9 THEORY OF OPERATION 9 ...
Страница 652: ...A 16 L90 Line Current Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 772: ...B 120 L90 Line Current Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 802: ...C 30 L90 Line Current Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 812: ...D 10 L90 Line Current Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 824: ...E 12 L90 Line Current Differential System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...
Страница 834: ...F 10 L90 Line Current Differential System GE Multilin F 3 WARRANTY APPENDIX F F ...
Страница 846: ...xii L90 Line Current Differential System GE Multilin INDEX ...