1
FUSE
Hi-Volt:
Current Rating: 2 A
Type:
5
×
20mm Slo-Blo Littelfuse
High Breaking Capacity
Model#:
215002
Lo-Volt:
Current Rating: 3.15 A
Type:
5
×
20mm Slo-Blo Littelfuse
High Breaking Capacity
Model#:
2153.15
External fuse must be used if the supply volt-
age exceeds 250 V.
DEMAND
Metered Values: Maximum Phase Current
3 Phase Real Power
3 Phase Apparent Power
3 Phase Reactive Power
Measurement Type: Rolling Demand
Demand Interval: 5 to 90 minutes in steps of 1
Update Rate:
1 minute
Elements:
Alarm
OTHER FEATURES
Pre-Trip Data
Event Recorder
Trace Memory
Starter Failure
Fault Simulation
VT Failure
ENVIRONMENT
Ambient Operating Temperature: –40°C to +60°C
Ambient Storage Temperature: –40°C to +80°C
Humidity:
Up to 90%, noncondensing.
Altitude:
Up to 2000 m
Pollution Degree: 2
It is recommended that the 469 be powered up
at least once per year to prevent deterioration
of electrolytic capacitors in the power supply.
BATTERY BACKUP
Used only when no control power to relay.
Life expectancy is
≥
10 years with no control power to relay
CASE
Fully drawout (automatic CT shorts)
Seal provision
Dust tight door
Panel or 19" rack mount
IP Class:
IP20-X
PRODUCTION TESTS
Thermal Cycling: Operational test at ambient, reducing to
–40°C and then increasing to 60°C
Dielectric Strength: 2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST!
TYPE TESTS
Dielectric Strength: Per IEC 255-5 and ANSI/IEEE C37.90
2.0 kV for 1 minute from relays, CTs,
VTs, power supply to Safety Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST
Insulation Resistance: IEC255-5 500 V DC, from relays,
CTs, VTs, power supply to Safety
Ground
DO NOT CONNECT FILTER GROUND TO
SAFETY GROUND DURING TEST
Transients:
ANSI C37.90.1 Oscillatory (2.5kV/1MHz)
ANSI C37.90.1 Fast Rise (5kV/10ns)
Ontario Hydro A-28M-82
IEC255-4 Impulse/High Frequency Dis-
turbance, Class III Level
Impulse Test:
IEC 255-5 0.5 Joule 5 kV
RFI:
50 MHz/15 W Transmitter
EMI:
C37.90.2 Electromagnetic Interference
@150 MHz and 450 MHz, 10 V/m
Static:
IEC 801-2 Static Discharge
Humidity:
95% non-condensing
Temperature:
–40°C to +60°C ambient
Environment:
IEC 68-2-38 Temperature/Humidity
Cycle
Vibration:
Sinusoidal Vibration 8.0 g for 72 hrs.
PACKAGING
Shipping Box:
12”
×
11”
×
10” (W
×
H
×
D)
30.5cm
×
27.9cm
×
25.4cm
Shipping Weight: 17 lbs Max / 7.7 kg
CERTIFICATION
ISO: Manufactured under an ISO9001 registered system.
UL: UL approved
CSA: CSA approved
CE: Conforms to EN 55011/CISPR 11, EN 50082-2
Conforms to IEC 947-1,1010-1
NOTE
NOTE
WARNING
WARNING
WARNING
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......