GE Power Management
469 Motor Management Relay
6-27
6 COMMUNICATIONS
6.4 MEMORY MAP
6
049F
Reserved
TIMERS
04A0
Motor Running Hours
1
100000
1
hr
F9
0
04A2
Time Between Starts Timer
0
500
1
min
F1
0
04A3
Start Timer 1
0
60
1
min
F1
0
04A4
Start Timer 2
0
60
1
min
F1
0
04A5
Start Timer 3
0
60
1
min
F1
0
04A6
Start Timer 4
0
60
1
min
F1
0
04A7
Start Timer 5
0
60
1
min
F1
0
04A8
Reserved
...
...
04BF
Reserved
469 MODEL
INFO.
04C0
Order Code
0
65535
1
N/A
FC136
N/A
04C1
Relay Serial Number
3050001
N/A
1
-
F9
N/A
04C3
Reserved
...
...
04DF
Reserved
CALIBRATION
INFO.
04E0
Original Calibration Date
N/A
N/A
N/A
N/A
F18
N/A
04E2
Last Calibration Date
N/A
N/A
N/A
N/A
F19
N/A
04E4
Reserved
...
...
04FF
Reserved
PHASORS
0500
Va Angle
0
359
1
°
F1
N/A
0501
Vb Angle
0
359
1
°
F1
N/A
0502
Vc Angle
0
359
1
°
F1
N/A
0503
Ia Angle
0
359
1
°
F1
N/A
0504
Ib Angle
0
359
1
°
F1
N/A
0505
Ic Angle
0
359
1
°
F1
N/A
0506
Reserved
...
...
0FFF
Reserved
Setpoints (Addresses 1000 to 1FFF)
PREFER-
ENCES
1000
Default Message Cycle Time
5
100
5
s
F2
20
1001
Default Message Timeout
10
900
1
s
F1
300
1002
Reserved
1003
Average Motor Load Calculation Period
1
90
1
min
F1
15
1004
Temperature Display Units
0
1
1
-
FC100
0
1005
Trace Memory Trigger Position
1
100
1
%
F1
25
1006
Trace Memory Buffers
1
16
1
cycles
F1
8
1007
Display Update Interval
1
60
1
s
F2
4
1008
Cyclic Load Filter Interval
0
32
1
cycles
F1
0
1009
Passcode (Write Only)
0
99999999
1
N/A
F12
0
100B
Encrypted Passcode (Read Only)
N/A
N/A
N/A
N/A
F12
N/A
100C
Reserved
Table 6–1: 469 MEMORY MAP (Sheet 10 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......