4-78
469 Motor Management Relay
GE Power Management
4.13 S12 ANALOG I/O
4 SETPOINT PROGRAMMING
4
c) ANALOG OUTPUT TABLE
Table 4–3: ANALOG OUTPUT PARAMETER SELECTION TABLE
PARAMETER NAME
RANGE / UNITS
STEP
DEFAULT
MIN.
MAX
Phase A Current
0 to 100000 A
1
0
100
Phase B Current
0 to 100000 A
1
0
100
Phase C Current
0 to 100000 A
1
0
100
Avg. Phase Current
0 to 100000 A
1
0
100
AB Line Voltage
50 to 20000 V
1
3200
4500
BC Line Voltage
50 to 20000 V
1
3200
4500
CA Line Voltage
50 to 20000 V
1
3200
4500
Avg. Line Voltage
50 to 20000 V
1
3200
4500
Phase AN Voltage
50 to 20000 V
1
1900
2500
Phase BN Voltage
50 to 20000 V
1
1900
2500
Phase CN Voltage
50 to 20000 V
1
1900
2500
Avg. Phase Voltage
50 to 20000 V
1
1900
2500
Hottest Stator RTD
–50 to +250
°
C or –58 to +482
°
F
1
0
200
Hottest Bearing RTD
–50 to +250
°
C or –58 to +482
°
F
1
0
200
Ambient RTD
–50 to +250
°
C or –58 to +482
°
F
1
-50
60
RTD #1 to 12
–50 to +250
°
C or –58 to +482
°
F
1
-50
250
Power Factor
0.01 to 1.00 lead/lag
0.01
0.8 lag
0.8 lead
Reactive Power
-50000 to 50000 kvar
1
0
750
Real Power
-50000 to 50000 kW
1
0
1000
Apparent Power
0 to 50000 kVA
1
0
1250
Thermal Capacity Used
0 to 100%
1
0
100
Relay Lockout Time
0 to 500 min.
1
0
150
Current Demand
0 to 100000 A
1
0
700
kvar Demand
0 to 50000 kvar
1
0
1000
kW Demand
0 to 50000 kW
1
0
1250
kVA Demand
0 to 50000 kVA
1
0
1500
Motor Load
0.00 to 20.00 x FLA
0.01
0.00
1.25
Analog Inputs 1-4
–50000 to +50000
1
0
+50000
Tachometer
100 to 7200 RPM
1
3500
3700
MWhrs
0.000 to 999999.999 MWhrs
0.001
50.000
100.000
Analog In Diff 1-2
–50000 to +50000
1
0
100
Analog In Diff 3-4
–50000 to +50000
1
0
100
Torque
0 to 999999.9
0.1
0
100
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......