6-30
469 Motor Management Relay
GE Power Management
6.4 MEMORY MAP
6 COMMUNICATIONS
6
...
11BF
Reserved
POWER
SYSTEM
11C0
Nominal System Frequency
0
1
1
-
FC107
0
11C1
System Phase Sequence
0
1
1
-
FC124
0
11C2
Speed2 Phase Sequence
0
1
1
-
FC124
0
11C3
Reserved
...
11C7
Reserved
SERIAL COM.
CONTROL
11C8
Serial Communication Control
0
1
1
-
FC103
0
11C9
Assign Start Control Relays
0
2
1
-
FC137
0
11CA
Reserved
...
11CF
Reserved
REDUCED
VOLTAGE
11D0
Reduced Voltage Starting
0
1
1
-
FC103
0
11D1
Control Relays for Reduced Voltage Starting
0
2
1
-
FC137
2
11D2
Transition On
0
2
1
-
FC108
0
11D3
Reduced Voltage Start Level
25
300
1
%FLA
F1
100
11D4
Reduced Voltage Start Timer
1
600
1
s
F1
200
11D5
Incomplete Sequence Trip Relays
0
3
1
-
FC111
0
11D6
Reserved
...
122F
Reserved
STARTER
STATUS
1230
Starter Status Switch
0
1
1
-
FC109
0
1231
Reserved
...
123F
Reserved
ASSIGNABLE
INPUTS
1240
Assignable Input 1 Function
0
18
1
-
FC110
0
1241
Assignable Input 2 Function
0
18
1
-
FC110
0
1242
Assignable Input 3 Function
0
18
1
-
FC110
0
1243
Assignable Input 4 Function
0
18
1
-
FC110
0
1244
Reserved
...
1259
Reserved
REMOTE
ALARM
125A
1st and 2nd char. of Remote Alarm Name
0
65535
1
-
F22
‘Re’
125B
3rd and 4th char. of Remote Alarm Name
0
65535
1
-
F22
‘mo’
...
1263
19th and 20th char. of Remote Alarm Name
0
65535
1
-
F22
‘ ‘
1264
Remote Alarm Function
1
2
1
-
FC115
2
1265
Remote Alarm Relays
0
6
1
-
FC113
0
1266
Remote Alarm Events
0
1
1
-
FC103
0
1267
Reserved
...
...
1279
Reserved
Table 6–1: 469 MEMORY MAP (Sheet 13 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......