GE Power Management
469 Motor Management Relay
6-47
6 COMMUNICATIONS
6.4 MEMORY MAP
6
1A1A
Reserved
...
1A1F
Reserved
REVERSE
POWER
1A20
Block Reverse Power From Start
0
5000
1
s
F1
0
1A21
Reverse Power Alarm
0
2
1
-
FC115
0
1A22
Reverse Power Alarm Relays
0
6
1
-
FC113
0
1A23
Reverse Power Alarm Level
1
25000
1
kW
F1
1
1A24
Reverse Power Alarm Delay
2
300
1
s
F1
10
1A25
Reverse Power Alarm Events
0
1
1
-
FC103
0
1A26
Reverse Power Trip
0
2
1
-
FC115
0
1A27
Reverse Power Trip Relays
0
3
1
-
FC111
0
1A28
Reverse Power Trip Level
1
25000
1
kW
F1
1
1A29
Reverse Power Trip Delay
2
300
1
s
F1
10
1A2A
Reserved
…
1A2F
Reserved
TORQUE
SETUP
1A30
Torque Metering
0
1
1
N/A
FC126
0
1A31
Stator Resistance
1
50000
1
mW
F26
4
1A32
Pole Pairs
2
128
2
-
F1
2
1A33
Torque Unit
0
1
1
-
FC148
0
1A34
Reserved
…
1A3F
Reserved
OVERTORQUE
SETUP
1A40
Overtorque Alarm
0
2
1
-
FC115
0
1A41
Overtorque Alarm Relays
0
6
1
-
FC113
0
1A42
Overtorque Alarm Level
10
9999999
1
Nm/ftlb
F10
40000
1A44
Overtorque Alarm Delay
2
300
1
s
F2
10
1A45
Overtorque Alarm Events
0
1
1
-
FC103
0
1A46
Reserved
...
1A7F
Reserved
TRIP
COUNTER
1A80
Trip Counter Alarm
0
2
1
-
FC115
0
1A81
Trip Counter Alarm Relays
0
6
1
-
FC113
0
1A82
Trip Counter Alarm Level
1
50000
1
-
F1
25
1A83
Trip Counter Alarm Events
0
1
1
-
FC103
0
1A84
Reserved
...
1A8F
Reserved
STARTER
FAILURE
1A90
Starter Failure Alarm
0
2
1
-
FC115
0
1A91
Starter Type
0
1
1
-
FC125
0
1A92
Starter Failure Alarm Relays
0
6
1
-
FC113
0
1A93
Starter Failure Alarm Delay
10
1000
10
ms
F1
100
Table 6–1: 469 MEMORY MAP (Sheet 30 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......