GE Power Management
469 Motor Management Relay
6-67
6 COMMUNICATIONS
6.4 MEMORY MAP
6
7 All Relays
8 No Relays
FC140
Unsigned
16 bit integer
GENERAL STATUS
bit 0 Relay in Service
bit 1 Active Trip Condition
bit 2 Active Alarm Condition
bit 3 Reserved
bit 4 Reserved
bit 5 Reserved
bit 6 Reserved
bit 7 Reserved
bit 8 Motor Stopped
bit 9 Motor Starting
bit 10 Motor Running
bit 11 Overload Pickup
bit 12 Unbalance Pickup
bit 13 Ground Pickup
bit 14 Hot RTD
bit 15 Loss of Load
FC141
Unsigned
16 bit integer
OUTPUT RELAY STATUS
bit 0 R1 Trip
bit 1 R2 Auxiliary
bit 2 R3 Auxiliary
bit 3 R4 Alarm
bit 4 R5 Block Start
bit 5 R6 Service
bit 6 – bit 15 Not Used
FC142
Unsigned
16 bit integer
TRIP COIL SUPERVISION SELECTION
0 Disabled
1 S2 Close
2 S2 Open/Close
FC143
Unsigned
16 bit integer
SINGLE VT SELECTION
0 Off
1 AN (Wye) AB (Delta)
2 BN (Wye) BC (Delta)
3 CN (Wye) N/A (Delta)
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 13 of 14)
FORMAT
CODE
TYPE
DEFINITION
FC144
Unsigned
16 bit integer
PULSED OUTPUT RELAY SELECTION
0 Off
1 Auxiliary2
2 Auxiliary3
3 Alarm
FC145
Unsigned
16 bit integer
ANALOG IN DIFFERENTIAL COMPARISON
0 % Difference
1 Absolute Difference
FC146
Unsigned
16 bit integer
ANALOG IN DIFFERENTIAL LOGIC
0 1>2 (or 3>4)
1 2>1 (or 4>3)
2 1<>2 (or 3<>4)
FC147
Unsigned
16 bit integer
ANALOG IN DIFFERENTIAL ACTIVE WHEN
0
Always
1
Start/Run
FC148
Unsigned
16 bit integer
TORQUE DISPLAY UNITS
0
Newton-meter
1
Foot-pound
Table 6–2: MEMORY MAP DATA FORMATS (Sheet 14 of 14)
FORMAT
CODE
TYPE
DEFINITION
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......