GE Power Management
469 Motor Management Relay
4-77
4 SETPOINT PROGRAMMING
4.13 S12 ANALOG I/O
4
4.13 S12 ANALOG I/O
4.13.1 ANALOG OUTPUTS 1 TO 4
The 469 has four analog output channels (4 to 20 mA or 0 to 1 mA as ordered). Each channel may be individ-
ually configured to represent a number of different measured parameters as shown in the table below. The
minimum value programmed represents the 4 mA output. The maximum value programmed represents the
20 mA output. If the minimum is programmed lower than the maximum the output will function in reverse. All
four of the outputs are updated once every 50 ms. Each parameter may only be used once.
For example, the analog output parameter may be chosen as
"Hottest Stator RTD"
for a 4 to 20 mA output. If the
minimum is set for
"0°C"
and the maximum is set for
"250°C"
, the analog output channel will output 4 mA when
the Hottest Stator RTD temperature is at 0°C, 12 mA when it is 125°C, and 20 mA when it is 250°C.
y
ANALOG OUTPUT 1
y
[ENTER] for more
ANALOG OUTPUT 1:
Therm. Capacity Used
Range: See Table 4–3: ANALOG OUTPUT PARAMETER
SELECTION TABLE.
THERM. CAPACITY USED
MIN: 0%
Range: 0 to 100%, step 1
THERM. CAPACITY USED
MAX: 100%
Range: 0 to 100%, step:1
y
ANALOG OUTPUT 2
y
[ENTER] for more
ANALOG OUTPUT 2:
Motor Load
Range: See Table 4–3: ANALOG OUTPUT PARAMETER
SELECTION TABLE.
MOTOR LOAD
MIN: 0.00 x FLA
Range: 0.00 to 20.00 x FLA, step 0.01
MOTOR LOAD
MAX: 1.50 x FLA
Range: 0.00 to 20.00 x FLA, step 0.01
y
ANALOG OUTPUT 3
y
[ENTER] for more
ANALOG OUTPUT 3:
Hottest Stator RTD
Range: See Table 4–3: ANALOG OUTPUT PARAMETER
SELECTION TABLE.
HOTTEST STATOR RTD
MIN: 0°C
Range: –50 to 250°C (or –58 to 482°F), step 1
HOTTEST STATOR RTD
MAX: 250°C
Range: –50 to 250°C (or –58 to 482°F), step 1
y
ANALOG OUTPUT 4
y
[ENTER] for more
ANALOG OUTPUT 4:
Real Power (kW)
Range: See Table 4–3: ANALOG OUTPUT PARAMETER
SELECTION TABLE.
REAL POWER (kW)
MIN: 0 kW
Range: –50000 to 50000 kW, step 1
REAL POWER (kW)
MAX: 100 kW
Range: –50000 to 50000 kW, step 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......