4-82
469 Motor Management Relay
GE Power Management
4.13 S12 ANALOG I/O
4 SETPOINT PROGRAMMING
4
4.13.4 ANALOG IN DIFF 3-4
This feature compares two of the analog inputs and activate alarms or trips based on the difference between
them. The difference can be of an absolute difference in units or a percentage difference. The second analog
input (4 for 3-4) is used as the reference value for percentage calculations. The comparison logic can also be
selected as one input greater than the other (
"3>4"
) or vice versa (
"4>3"
) or as absolute difference (
"3<>4"
).
Note that the compared analog inputs must be programmed with the same unit type prior to using this feature.
y
ANALOG IN DIFF 3-4
y
[ENTER] for more
ANALOG IN DIFF 3-4:
Disabled
Range: Disabled, Enabled
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
NAME: Analog 3-4
Range: 12 alphanumeric characters
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
COMPARISON: % Diff
Range: % Diff, Abs. Diff
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
LOGIC: 3<>4
Range: 1<>2, 1>2, 2>1
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
ACTIVE: Always
Range: Always, Start/Run
Message seen only if Analog Inputs 1 and 2 are enabled.
A/I DIFF 1-2 BLOCK
FROM START: 0 s
Range: 0 to 5000 sec.; Step: 1
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
ALARM: Off
Range: Off, Latched, Unlatched
Message seen only if Analog Inputs 1 and 2 are enabled.
ASSIGN ALARM RELAYS:
Alarm
Range:
Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
ALARM LEVEL: 10%
Range: 0 to 500%; Step: 1.
Seen only if Analog Inputs 1 and 2 are enabled and % Diff is Set
A/I DIFF 1-2 ALARM
LEVEL: 10 Units
Range: 0 to 50000; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and Abs Diff is Set
ANALOG IN DIFF 3-4
ALARM DELAY: 0.1 s
Range: 0.1 to 300.0 sec.; Step: 0.1
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
EVENTS: Off
Range: On, Off
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
TRIP: Off
Range: Off, Latched, Unlatched
Message seen only if Analog Inputs 1 and 2 are enabled.
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3
Trip & Auxiliary3
Message seen only if Analog Inputs 1 and 2 are enabled.
ANALOG IN DIFF 3-4
TRIP LEVEL: 10%
Range: 0 to 500%; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and % Diff is set.
ANALOG IN DIFF 3-4
TRIP LEVEL: 10 Units
Range: 0 to 50000; Step: 1
Seen only if Analog Inputs 1 and 2 are enabled and Abs Diff is Set
ANALOG IN DIFF 3-4
TRIP DELAY: 0.1 s
Range: 0.1 to 300.0 sec.; Step: 0.1
Message seen only if Analog Inputs 1 and 2 are enabled.
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......