4.14 S13 469 TESTING
4
4.14.3 FAULT SETUP
The values entered under Fault Values will be substituted for the measured values in the 469 when the simula-
tion mode is
"Simulate Fault"
.
y
FAULT SETUP
y
[ENTER] for more
FAULT CURRENT
PHASE A: 0.00 x CT
Range: 0.00 to 20.00 x CT, step 0.01
FAULT CURRENT
PHASE B: 0.00 x CT
Range: 0.00 to 20.00 x CT, step 0.01
FAULT CURRENT
PHASE C: 0.00 x CT
Range: 0.00 to 20.00 x CT, step 0.01
FAULT GROUND
CURRENT: 0.0 A
Range: 0.0 to 5000.0 A, step 0.1
FAULT VOLTAGES
VLINE: 1.00 x RATED
Range: 0.00 to 1.10 x RATED, step 0.01
FAULT CURRENT
LAGS VOLTAGE: 0°
Range: 0 to 359°, step 1
FAULT DIFF AMPS
IDIFF: 0.00 x CT
Range: 0.00 to 1.10 x RATED, step 0.01
FAULT STATOR
RTD TEMP: 40°C
Range: –50 to 250°C, step 1
FAULT BEARING
RTD TEMP: 40°C
Range: –50 to 250°C, step 1
FAULT OTHER
RTD TEMP: 40°C
Range: –50 to 250°C, step 1
FAULT AMBIENT
RTD TEMP: 40°C
Range: –50 to 250°C, step 1
FAULT SYSTEM
FREQUENCY: 60.0 Hz
Range: 45.0 to 70.0 Hz, step 0.1
FAULT ANALOG
INPUT 1: 0%
Range: 0 to 100%, step 1
FAULT ANALOG
INPUT 2: 0%
Range: 0 to 100%, step 1
FAULT ANALOG
INPUT 3: 0%
Range: 0 to 100%, step 1
FAULT ANALOG
INPUT 4: 0%
Range: 0 to 100%, step 1
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......