GE Power Management
469 Motor Management Relay
A-1
APPENDIX A
A.1 COMMISSIONING
A
APPENDIX A APPENDIX AA.1 COMMISSIONING
A.1.1 COMMISSIONING SUMMARY
Table A–1: SETPOINTS PAGE 1 – 469 SETUP
DESCRIPTION
DEFAULT
USER VALUE
PASSCODE
Passcode
----
PREFERENCES
Default Message Cycle Time
2.0 s
Default Message Timeout
300 s
Avg. Motor Load Calc. Period
15 min.
Temperature Display
Celsius
Trace Memory Trigger Pos.
25%
Trace Memory Buffers
8 x 14 cycles
Display Update Interval
0.4 s
Filter Interval
0 cycles
SERIAL PORTS
Slave Address
254
Comp. RS485 Baud Rate
9600 baud
Comp. RS485 Parity
None
Aux. RS485 Baud Rate
9600 baud
Aux. RS485 Parity
None
MESSAGE SCRATCHPAD
Text 1
Text 2
Text 3
Text 4
Text 5
Table A–2: SETPOINTS PAGE 2 – SYSTEM SETUP
DESCRIPTION
DEFAULT
USER VALUE
CURRENT SENSING
Phase CT Primary
Not Programmed
Motor Full Load Amps
Not Programmed
Ground CT
Multilin 50:0.025
Ground CT Primary
100 A
Phase Differential CT
None
Phase Differential CT Primary
100 A
Enable 2-Speed Motor Prot.
No
Speed2 Phase CT Primary
100 A
Speed2 Motor FLA
1 A
VOLTAGE SENSING
VT Connection Type
None
Enable Single VT Connection
Off
Voltage Transformer Ratio
35.00:1
Motor Nameplate Voltage
4000 V
POWER SYSTEM
Nominal System Frequency
60 Hz
System Phase Sequence
ABC
Speed2 Phase Sequence
ABC
SERIAL COMMUNICATION CONTROL
Serial Communication Ctrl.
Off
Assign Start Control Relays
Auxiliary2
REDUCED VOLTAGE
Reduced Voltage Starting
Off
Assign Control Relays
Auxiliary3
Transition On
Current Only
Assign Trip Relays
Trip
Reduced Voltage Start Level
100% FLA
Reduced Voltage Start Timer
200 s
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......