6-60
469 Motor Management Relay
GE Power Management
6.4 MEMORY MAP
6 COMMUNICATIONS
6
EVENT
RECORDER
continued
…
30DF
Reserved
30E0
Event Temp. of Hottest Stator RTD (in Fahr.)
–58
482
1
°F
F4
32
30E1
Event Temp. of Hottest Bearing RTD (in Fahr.)
–58
482
1
°F
F4
32
30E2
Event Temp. of Hottest Other RTD (in Fahr.)
–58
482
1
°F
F4
32
30E3
Event Ambient RTD Temperature (in Fahr.)
–58
482
1
°F
F4
32
TRACE
MEMORY
30E4
Reserved
...
30EF
Reserved
30F0
Trace Number Selector
1
65535
1
-
F1
0
30F1
Trace Memory Channel Selector
0
9
1
-
F1
0
30F2
Trace Memory Date
N/A
N/A
N/A
N/A
F18
N/A
30F4
Trace Memory Time
N/A
N/A
N/A
N/A
F19
N/A
30F6
Trace Trigger Cause
0
131
1
-
FC134
N/A
30F7
Number of Samples per Trace
1
768
1
-
F1
N/A
30F8
Number of Traces Taken
0
65535
1
-
F1
N/A
30F9
Reserved
30FF
Reserved
3100
First Trace Memory Sample
–32767
32767
1
-
F4
0
...
...
3400
Last Trace Memory Sample
–32767
32767
1
-
F4
0
3401
Reserved
...
...
3FFF
Reserved
Table 6–1: 469 MEMORY MAP (Sheet 43 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......