![GE MOTOR MANAGEMENT RELAY 469 Скачать руководство пользователя страница 224](http://html.mh-extra.com/html/ge/motor-management-relay-469/motor-management-relay-469_instruction-manual_131868224.webp)
6-52
469 Motor Management Relay
GE Power Management
6.4 MEMORY MAP
6 COMMUNICATIONS
6
ANALOG
OUTPUTS
continued
1BEC
RTD #10 Minimum (in Fahrenheit)
–58
482
1
°F
F4
–57
1BED
RTD #10 Maximum (in Fahrenheit)
–58
482
1
°F
F4
482
1BEE
RTD #11 Minimum (in Fahrenheit)
–58
482
1
°F
F4
–57
1BEF
RTD #11 Maximum (in Fahrenheit)
–58
482
1
°F
F4
482
1BF0
RTD #12 Minimum (in Fahrenheit)
–58
482
1
°F
F4
–57
1BF1
RTD #12 Maximum (in Fahrenheit)
–58
482
1
°F
F4
482
1BF2
Reserved
...
...
1BF7
Reserved
1BF8
Analog Input Diff 1-2 Minimum
–50000
50000
1
-
F12
0
1BFA
Analog Input Diff 1-2 Maximum
–50000
50000
1
-
F12
100
1BFC
Analog Input Diff 3-4 Minimum
–50000
50000
1
-
F12
0
1BFE
Analog Input Diff 3-4 Maximum
–50000
50000
1
-
F12
100
1C00
Reserved
...
1C0A
Reserved
ANALOG
INPUT 1
1C0B
Analog Input 1 Setup
0
3
1
-
FC129
0
1C0C
Reserved
...
1C0F
Reserved
1C10
1st and 2nd char. of Analog Input 1 Units
0
65535
1
-
F22
‘Un’
...
1C12
5th and 6th char. of Analog Input 1 Units
0
65535
1
-
F22
‘ ‘
1C13
Analog Input 1 Minimum
–50000
50000
1
-
F12
0
1C15
Analog Input 1 Maximum
–50000
50000
1
-
F12
100
1C17
Block Analog Input 1 From Start
0
5000
1
s
F1
0
1C18
Analog Input 1 Alarm
0
2
1
-
FC115
0
1C19
Analog Input 1 Alarm Relays
0
6
1
-
FC113
0
1C1A
Analog Input 1 Alarm Level
–50000
50000
1
-
F12
10
1C1C
Analog Input 1 Alarm Pickup
0
1
1
-
FC130
0
1C1D
Analog Input 1 Alarm Delay
1
3000
1
s
F2
1
1C1E
Analog Input 1 Alarm Events
0
1
1
-
FC103
0
1C1F
Analog Input 1 Trip
0
2
1
-
FC115
0
1C20
Analog Input 1 Trip Relays
0
3
1
-
FC111
0
1C21
Analog Input 1 Trip Level
–50000
50000
1
-
F12
20
1C23
Analog Input 1 Trip Pickup
0
1
1
-
FC130
0
1C24
Analog Input 1 Trip Delay
1
3000
1
s
F2
1
1C25
1st and 2nd char. of Analog Input 1 Name
0
65535
1
-
F22
‘An’
...
1C2A
11th and 12th char. of Analog Input 1 Name
0
65535
1
-
F22
‘ ‘
1C2B
Reserved
...
1C4A
Reserved
Table 6–1: 469 MEMORY MAP (Sheet 35 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......