4-4
469 Motor Management Relay
GE Power Management
4.2 S1 469 SETUP
4 SETPOINT PROGRAMMING
4
4.2 S1 469 SETUP
4.2.1 PASSCODE
a) FUNCTION
A passcode access security feature is provided in addition to the setpoint access jumper. When shipped from
the factory, the passcode is defaulted to 0. Passcode protection is ignored when the passcode is 0. In this
case, only the setpoint access jumper is required for changing setpoints from the front panel. Passcodes are
also ignored when programming setpoints via the RS485 port. However when programming setpoints using
the front RS232 port and the 469PC software, a passcode is required (if enabled).
b) ENABLING PASSCODE PROTECTION
To enable passcode protection on a new relay, press
then
until
is displayed. Select "Yes" and follow directions to enter a new passcode from 1-8 digits.
Once a passcode other than 0 is programmed, it must be entered each time setpoint access is restricted. If a
non-zero passcode has been programmed and setpoint access is restricted, then the following message
appears when entering the
PASSCODE
subgroup:
Enter the correct passcode. A flash message will advise if the code is incorrect and allows a retry. If the pass-
code is correct and the setpoint access jumper is installed, the following message appears:
Setpoints can now be entered. Press
to exit the
PASSCODE
group and program the appropriate set-
points. If no keys are pressed for 5 minutes, programming access will no longer be allowed and the passcode
must be re-entered. Removing the setpoint access jumper or selecting
"Restricted"
at the
SETPOINT ACCESS
mes-
sage will also disable setpoint access immediately.
If a new passcode is required, gain setpoint access by entering the valid passcode as described above. Then
press
to display the
CHANGE PASSCODE
message and follow directions.
If an invalid passcode is entered, an encrypted passcode may be viewed by pressing the
key. Consult
the factory service department with this number if the currently programmed passcode is unknown. Using a
deciphering program, the passcode can be determined.
y
PASSCODE
y
[ENTER] for more
ENTER PASSCODE FOR
ACCESS:
Range:
1 to 8 numeric digits. This message is seen only if the
passcode is not 0 and setpoint access is restricted.
SETPOINT ACCESS:
Permitted
Range:
Permitted, Restricted This message is seen only if the
passcode is 0 or setpoint access is permitted.
CHANGE PASSWORD:
No
Range:
No, Yes. This message is seen only if the passcode is 0
or setpoint access is permitted.
CHANGE PASSCODE?
No
ENTER NEW PASSCODE
FOR ACCESS:
ENTER NEW PASSCODE
AGAIN:
ENTER PASSCODE FOR
ACCESS:
SETPOINT ACCESS:
Permitted
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
ENTER
MESSAGE
ESCAPE
MESSAGE
HELP
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......