GE Power Management
469 Motor Management Relay
6-19
6 COMMUNICATIONS
6.4 MEMORY MAP
6
Actual Values (Addresses 0200 -0FFF)
MOTOR
STATUS
0200
Motor Status
0
4
1
-
FC133
0
0201
Motor Thermal Capacity Used
0
100
1
%
F1
0
0202
Estimated Time to Trip on Overload
–1
99999
1
s
F20
–1
0204
Motor Speed
0
1
1
-
FC135
0
0205
Communication Setpoint Access
0
1
N/A
N/A
F126
N/A
0206
Reserved
...
...
020F
Reserved
SYSTEM
STATUS
0210
General Status
0
65535
1
-
FC140
0
0211
Output Relay Status
0
63
1
-
FC141
0
0212
Reserved
...
021F
Reserved
LAST TRIP
DATA ALARM
0220
Cause of Last Trip
0
45
1
-
FC134
0
0221
Time of Last Trip (2 words)
N/A
N/A
N/A
N/A
F19
N/A
0223
Date of Last Trip (2 words)
N/A
N/A
N/A
N/A
F18
N/A
0225
Motor Speed During Trip
0
1
1
-
FC135
0
0226
Pre-Trip Tachometer RPM
0
3600
1
RPM
F1
0
0227
Phase A Pre-Trip Current
0
100000
1
A
F9
0
0229
Phase B Pre-Trip Current
0
100000
1
A
F9
0
022B
Phase C Pre-Trip Current
0
100000
1
A
F9
0
022D
Pre-Trip Motor Load
0
2000
1
FLA
F3
0
022E
Pre-Trip Current Unbalance
0
100
1
%
F1
0
022F
Pre-Trip Ground Current
0
500000
1
A
F11
0
0231
Phase A Pre-Trip Differential Current
0
5000
1
A
F1
0
0232
Phase B Pre-Trip Differential Current
0
5000
1
A
F1
0
0233
Phase C Pre-Trip Differential Current
0
5000
1
A
F1
0
0234
Hottest Stator RTD During Trip
0
12
1
-
F1
0
0235
Pre-Trip Temperature of Hottest Stator RTD
–50
250
1
°C
F4
0
0236
Hottest Bearing RTD During Trip
0
12
1
-
F1
0
0237
Pre-Trip Temperature of Hottest Bearing RTD
–50
250
1
°C
F4
0
0238
Hottest Other RTD During Trip
0
12
1
-
F1
0
0239
Pre-Trip Temperature of Hottest Other RTD
–50
250
1
°C
F4
0
023A
Hottest Ambient RTD During Trip
0
12
1
-
F1
0
023B
Pre-Trip Ambient RTD Temperature
–50
250
1
°C
F4
0
023C
Pre-Trip Voltage Vab
0
20000
1
V
F1
0
023D
Pre-Trip Voltage Vbc
0
20000
1
V
F1
0
023E
Pre-Trip Voltage Vca
0
20000
1
V
F1
0
023F
Pre-Trip Voltage Van
0
20000
1
V
F1
0
0240
Pre-Trip Voltage Vbn
0
20000
1
V
F1
0
0241
Pre-Trip Voltage Vcn
0
20000
1
V
F1
0
0242
Pre-Trip System Frequency
0
12000
1
Hz
F3
0
Table 6–1: 469 MEMORY MAP (Sheet 2 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......