GE Power Management
469 Motor Management Relay
6-7
6 COMMUNICATIONS
6.2 SUPPORTED MODBUS FUNCTIONS
6
Example 2: Request slave 11 to respond with status of digital inputs 1 to 4:
Digital Input
Status
D1: Access
Closed
D2: Test
Open
D3: Starter Status
Open
D4: Emergency Restart
Open
D5: Remote Reset
Closed
D6: Assignable Input 1
Closed
D7: Assignable Input 2
Closed
D8: Assignable Input 3
Open
D9: Assignable Input 4
Closed
Bit Mask (LSB)
0111 0001
MASTER TRANSMISSION:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
0B
message for slave 11
FUNCTION CODE
1
02
read digital input status
STARTING DIGITAL INPUT
2
00 01
starting at digital input 1
NUMBER OF DIGITAL INPUTS
2
00 04
4 digital inputs (i.e. D1, D2, D3, D4)
CRC
2
28 A3
CRC calculated by the master
SLAVE RESPONSE:
BYTES
EXAMPLE / DESCRIPTION
SLAVE ADDRESS
1
0B
response message from slave 11
FUNCTION CODE
1
02
read relay coil status
BYTE COUNT
1
01
2 byte bit mask
BIT MASK
2
01
bit mask of requested digital input
CRC
2
63 90
CRC calculated by the slave