6-38
469 Motor Management Relay
GE Power Management
6.4 MEMORY MAP
6 COMMUNICATIONS
6
ACCELERA-
TION TIMER
16D0
Acceleration Timer Trip
0
2
1
-
FC115
0
16D1
Acceleration Timer Trip Relays
0
3
1
-
FC111
0
16D2
Acceleration Timer from Start
10
2500
1
s
F2
100
16D3
Reserved
...
16DF
Reserved
START
INHIBIT
16E0
Start Inhibit Block
0
1
1
-
FC103
0
16E1
Thermal Capacity Used Margin
0
25
1
%
F1
25
16E2
Reserved
...
16EF
Reserved
JOGGING
BLOCK
16F0
Jogging Block
0
1
1
-
FC103
0
16F1
Maximum Starts/Hour Permissible
1
5
1
-
F1
3
16F2
Time Between Starts
0
500
1
min
F1
10
16F3
Reserved
...
16FF
Reserved
RESTART
BLOCK
1700
Restart Block
0
1
1
-
FC103
0
1701
Restart Block Time
1
50000
1
s
F1
1
1702
Reserved
...
177F
Reserved
RTD TYPES
1780
Stator RTD Type
0
3
1
-
FC120
0
1781
Bearing RTD Type
0
3
1
-
FC120
0
1782
Ambient RTD Type
0
3
1
-
FC120
0
1783
Other RTD Type
0
3
1
-
FC120
0
1784
Reserved
...
178F
Reserved
RTD #1
1790
RTD #1 Application
0
4
1
-
FC121
1
1791
RTD #1 Alarm
0
2
1
-
FC115
0
1792
RTD #1 Alarm Relays
0
6
1
-
FC113
0
1793
RTD #1 Alarm Temperature
1
250
1
°C
F1
130
1794
RTD #1 Alarm Events
0
1
1
-
FC103
0
1795
RTD #1 Trip
0
2
1
-
FC115
0
1796
RTD #1 Trip Voting
1
12
1
-
FC122
1
1797
RTD #1 Trip Relays
0
3
1
-
FC111
0
1798
RTD #1 Trip Temperature
1
250
1
°C
F1
155
Table 6–1: 469 MEMORY MAP (Sheet 21 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT
Содержание MOTOR MANAGEMENT RELAY 469
Страница 2: ......
Страница 4: ......
Страница 12: ......
Страница 22: ......
Страница 50: ......
Страница 142: ......
Страница 240: ......
Страница 254: ......
Страница 272: ......
Страница 286: ......
Страница 290: ......
Страница 294: ......
Страница 298: ......
Страница 300: ......
Страница 302: ......