Bad state (11) is indicated when the
BREAKER 1 OPEN
and
BREAKER 1 CLOSED
operands are Off.
•
XCBR1.ST.BlkOpn: This is the state of the block open command logic. When true, breaker open commands from IEC
61850 clients will be rejected.
•
XCBR1.ST.BlkCls: This is the state of the block close command logic. When true, breaker close commands from IEC
61850 clients will be rejected.
•
XCBR1.CO.Pos: This is where IEC 61850 clients can issue open or close commands to the breaker. SBO control with
normal security is the only supported IEC 61850 control model.
•
XCBR1.CO.BlkOpn: This is where IEC 61850 clients can issue block open commands to the breaker. Direct control
with normal security is the only supported IEC 61850 control model.
•
XCBR1.CO.BlkCls: This is where IEC 61850 clients can issue block close commands to the breaker. Direct control
with normal security is the only supported IEC 61850 control model.
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...