GE Multilin
B90 Low Impedance Bus Differential System
5-25
5 SETTINGS
5.2 PRODUCT SETUP
5
The menu for the binary input points (DNP) or MSP points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP / IEC104 POINT LISTS
BINARY INPUT / MSP POINTS
Up to 256 binary input points can be configured for the DNP or IEC 60870-5-104 protocols. The points are configured by
assigning an appropriate FlexLogic operand. Refer to the
Introduction to FlexLogic
section in this chapter for the full range
of assignable operands.
The menu for the analog input points (DNP) or MME points (IEC 60870-5-104) is shown below.
PATH: SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP / IEC104 POINT LISTS
ANALOG INPUT / MME POINTS
Up to 256 analog input points can be configured for the DNP or IEC 60870-5-104 protocols. The analog point list is config-
ured by assigning an appropriate FlexAnalog parameter to each point. Refer to Appendix A:
FlexAnalog Parameters
for the
full range of assignable parameters.
The DNP / IEC 60870-5-104 point lists always begin with point 0 and end at the first “Off” value. Since DNP / IEC
60870-5-104 point lists must be in one continuous block, any points assigned after the first “Off” point are ignored.
Changes to the DNP / IEC 60870-5-104 point lists will not take effect until the B90 is restarted.
BINARY INPUT / MSP
POINTS
Point:
0
Off
Range: FlexLogic operand
MESSAGE
Point:
1
Off
Range: FlexLogic operand
MESSAGE
Point:
255
Off
Range: FlexLogic operand
ANALOG INPUT / MME
POINTS
Point:
0
Off
Range: any FlexAnalog parameter
MESSAGE
Point:
1
Off
Range: any FlexAnalog parameter
MESSAGE
Point:
255
Off
Range: any FlexAnalog parameter
NOTE
NOTE
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...