GE Multilin
B90 Low Impedance Bus Differential System
5-39
5 SETTINGS
5.2 PRODUCT SETUP
5
The B90 supports the IEC 60870-5-104 protocol. The B90 can be used as an IEC 60870-5-104 slave device connected to
a maximum of two masters (usually either an RTU or a SCADA master station). Since the B90 maintains two sets of IEC
60870-5-104 data change buffers, no more than two masters should actively communicate with the B90 at one time.
The
IEC ------- DEFAULT THRESHOLD
settings are used to determine when to trigger spontaneous responses containing
M_ME_NC_1 analog data. These settings group the B90 analog data into types: current, voltage, power, energy, and other.
Each setting represents the default threshold value for all M_ME_NC_1 analog points of that type. For example, to trigger
spontaneous responses from the B90 when any current values change by 15 A, the
IEC CURRENT DEFAULT THRESHOLD
set-
ting should be set to 15. Note that these settings are the default values of the deadbands. P_ME_NC_1 (parameter of mea-
sured value, short floating point value) points can be used to change threshold values, from the default, for each individual
M_ME_NC_1 analog point. Whenever power is removed and re-applied to the B90, the default thresholds are in effect.
The B90 relay does not support power metering. As such, the
IEC POWER DEFAULT THRESHOLD
setting is not appli-
cable.
The B90 relay does not support energy metering. As such, the
IEC ENERGY DEFAULT THRESHOLD
setting is not appli-
cable.
The IEC 60870-5-104 and DNP protocols cannot be used simultaneously. When the IEC 60870-5-104 FUNCTION
setting is set to “Enabled”, the DNP protocol does not operate. When this setting is changed, it takes effect when
power to the relay is cycled (off-to-on).
5.2.7 MODBUS USER MAP
PATH: SETTINGS
PRODUCT SETUP
MODBUS USER MAP
The Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desired
address in the
ADDRESS
line (converted from hex to decimal format). The corresponding value displays in the
VALUE
line. A
value of “0” in subsequent register
ADDRESS
lines automatically returns values for the previous
ADDRESS
lines incremented
by “1”. An address value of “0” in the initial register means “none” and values of “0” display for all registers. Different
ADDRESS
values can be entered as required in any of the register positions.
5.2.8 REAL TIME CLOCK
a) MAIN MENU
PATH: SETTINGS
PRODUCT SETUP
REAL TIME CLOCK
MODBUS USER MAP
ADDRESS
1:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
MESSAGE
ADDRESS
2:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
MESSAGE
ADDRESS
3:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
MESSAGE
ADDRESS 256:
0
VALUE:
0
Range: 0 to 65535 in steps of 1
REAL TIME
CLOCK
SYNCRONIZING SOURCE:
None
Range: None, PP/IRIG-B/PTP/SNTP, IRIG-B/PP/PTP/
SNTP, PP/PTP/IRIG-B/SNTP
MESSAGE
REAL TIME CLOCK
EVENTS: Disabled
Range: Disabled, Enabled
MESSAGE
IRIG-B SIGNAL TYPE:
None
Range: None, DC Shift, Amplitude Modulated
NOTE
NOTE
NOTE
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...