GE Multilin
B90 Low Impedance Bus Differential System
B-61
APPENDIX B
B.4 MEMORY MAPPING
B
F142
ENUMERATION: EVENT RECORDER ACCESS FILE TYPE
0 = All Record Data, 1 = Headers Only, 2 = Numeric Event Cause
F143
UR_UINT32: 32 BIT ERROR CODE (F141 specifies bit number)
A bit value of 0 = no error, 1 = error
F144
ENUMERATION: FORCED CONTACT INPUT STATE
0 = Disabled, 1 = Open, 2 = Closed
F145
ENUMERATION: ALPHABET LETTER
F146
ENUMERATION: MISCELLANEOUS EVENT CAUSES
30
Any Minor Error
31
Any Major Error
33
Maintenance Alert
64
Maintenance Alert
65
IEC 61850 Data Set
66
Aggregator Error
67
Unit Not Calibrated
68
Settings Save Error
69
SRAM Data Error
70
Program Memory
71
Watchdog Error
72
Low On Memory
73
Prototype Firmware
74
Module Failure 01
75
Module Failure 02
76
Module Failure 03
77
Module Failure 04
78
Module Failure 05
79
Module Failure 06
80
Module Failure 07
81
Module Failure 08
82
Module Failure 09
83
Incompatible H/W
84
Module Failure 10
85
Module Failure 11
86
Module Failure 12
87
High ENET Traffic
89
Relay Restart
90
FGM Failure
91
FGM Failure
92
FGM Failure
93
FGM Failure
94
FGM Failure
95
FGM Error
96
Maintenance Alert
97
PHY Monitor
98
Storage Media Alarm
99
Wrong Transceiver
Bitmask
Error
bitmask type
bitmask type
bitmask type
bitmask type
0
null
7
G
14
N
21
U
1
A
8
H
15
O
22
V
2
B
9
I
16
P
23
W
3
C
10
J
17
Q
24
X
4
D
11
K
18
R
25
Y
5
E
12
L
19
S
26
Z
6
F
13
M
20
T
bitmask
definition
0
Events Cleared
1
Oscillography Triggered
2
Date/time Changed
3
Default Settings Loaded
4
Test Mode Forcing On
5
Test Mode Forcing Off
6
Power On
7
Power Off
8
Relay In Service
9
Relay Out Of Service
10
Watchdog Reset
11
Oscillography Clear
12
Reboot Command
13
Led Test Initiated
14
Flash Programming
15
Fault Report Trigger
16
User Programmable Fault Report Trigger
17
---
18
Reload CT/VT module Settings
19
---
20
Ethernet Port 1 Offline
21
Ethernet Port 2 Offline
22
Ethernet Port 3 Offline
23
Ethernet Port 4 Offline
24
Ethernet Port 5 Offline
25
Ethernet Port 6 Offline
26
Test Mode Isolated
27
Test Mode Forcible
28
Test Mode Disabled
29
Temperature Warning On
30
Temperature Warning Off
31
Unauthorized Access
32
System Integrity Recovery
33
System Integrity Recovery 06
34
System Integrity Recovery 07
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...