GE Multilin
B90 Low Impedance Bus Differential System
5-141
5 SETTINGS
5.7 INPUTS/OUTPUTS
5
The GOOSE analog input FlexAnalog values are available for use in other B90 functions that use FlexAnalog values.
5.7.12 IEC 61850 GOOSE INTEGERS
PATH: SETTINGS
INPUTS/OUTPUTS
IEC 61850 GOOSE UINTEGERS
GOOSE UINTEGER INPUT 1(16)
The IEC 61850 GOOSE uinteger inputs feature allows the transmission of FlexInteger values between any two UR-series
devices. The following settings are available for each GOOSE uinteger input.
•
UINTEGER 1 DEFAULT
: This setting specifies the value of the GOOSE uinteger input when the sending device is
offline and the
UINTEGER 1 DEFAULT MODE
is set to “Default Value”.This setting is stored as a 32-bit unsigned integer
number.
•
UINTEGER 1 DEFAULT MODE
: When the sending device is offline and this setting is “Last Known”, the value of the
GOOSE uinteger input remains at the last received value. When the sending device is offline and this setting value is
“Default Value”, then the value of the GOOSE uinteger input is defined by the
UINTEGER 1 DEFAULT
setting.
The GOOSE integer input FlexInteger values are available for use in other B90 functions that use FlexInteger values.
PHASE ANGLE
BASE
= 360 degrees (see the UR angle referencing convention)
POWER FACTOR
PF
BASE
= 1.00
RTDs
BASE = 100°C
SOURCE CURRENT
I
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE POWER
P
BASE
= maximum value of V
BASE
I
BASE
for the +IN and –IN inputs
SOURCE VOLTAGE
V
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
GOOSE UINTEGER
INPUT 1
UINTEGER 1
DEFAULT:
1000
Range: 0 to 429496295 in steps of 1
MESSAGE
UINTEGER 1
DEFAULT
MODE: Default Value
Range: Default Value, Last Known
Table 5–20: GOOSE ANALOG INPUT BASE UNITS (Sheet 2 of 2)
ELEMENT
BASE UNITS
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...