APPLICATION EXAMPLE:
For illustration, assume the F7 current is monitored for Breaker Failure protection of a given breaker as shown below.
Figure 5–46: DIRECT I/O SAMPLE CONFIGURATION FOR BREAKER FAILURE PROTECTION
The Protection IEDs 1, 2, and 3 (
B90 FUNCTION
set to "Protection") send the Breaker Fail current supervision flags over the
Direct I/O communications. Assume bits 13, 14, and 15 are used for this purpose as follows:
For IED 1:
DIRECT OUTPUT DEVICE ID
: "1" (this is an originating device)
DIRECT OUT 13 OPERAND
: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND
: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND
: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
For IED 2:
DIRECT OUTPUT DEVICE ID
: "2" (this is an originating device)
DIRECT OUT 13 OPERAND
: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND
: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND
: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
For IED 3:
DIRECT OUTPUT DEVICE ID
: "3" (this is an originating device)
DIRECT OUT 13 OPERAND
: "BKRSUPV 3 SUPV OP" (this operand drives output number 13)
DIRECT OUT 14 OPERAND
: "BKRSUPV 3 HISET OP" (this operand drives output number 14)
DIRECT OUT 15 OPERAND
: "BKRSUPV 3 LOSET OP" (this operand drives output number 15)
The above 9 flags must be received at the IED 4. Assume Direct Inputs 1 through 9 are to be used for this purpose. This is
accomplished with the following settings:
For IED 4:
DIRECT INPUT 1 DEVICE
: "1" (message received from IED 1)
DIRECT INPUT 1 BIT NUMBER
: "13" (this is BKRSUPV 3 SUPV OP for Phase A)
DIRECT INPUT 2 DEVICE
: "1" (message received from IED 1)
DIRECT INPUT 2 BIT NUMBER
: "14" (this is BKRSUPV 3 HISET OP for Phase A)
DIRECT INPUT 3 DEVICE
: "1" (message received from IED 1)
DIRECT INPUT 3 BIT NUMBER
: "15" (this is BKRSUPV 3 LOSET OP for Phase A)
DIRECT INPUT 4 DEVICE
: "2" (message received from IED 2)
DIRECT INPUT 4 BIT NUMBER
: "13" (this is BKRSUPV 3 SUPV OP for Phase B)
DIRECT INPUT 5 DEVICE
: "2" (message received from IED 2)
DIRECT INPUT 5 BIT NUMBER
: "14" (this is BKRSUPV 3 HISET OP for Phase B)
DIRECT INPUT 6 DEVICE
: "2" (message received from IED 2)
DIRECT INPUT 6 BIT NUMBER
: "15" (this is BKRSUPV 3 LOSET OP for Phase B)
DIRECT INPUT 7 DEVICE
: "3" (message received from IED 3)
DIRECT INPUT 7 BIT NUMBER
: "13" (this is BKRSUPV 3 SUPV OP for Phase C)
836759A3.CDR
Received as DIRECT
INPUTs 1 through 9
s
ent
as
bi
ts
no.
13,
14
and
15
BKR FAIL SUPV OP
BKR FAIL HISET OP
BKR FAIL LOSET OP
phase A current, wired to F7
phase B current, wired to F7
phase C current, wired to F7
BF CT = F7
IED 4
IED 1
IED 2
IED 3
breaker auxiliary switches
(if used for BF)
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...