5-12
B90 Low Impedance Bus Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
•
In CyberSentry, password encryption is not supported.
d) SESSION SETTINGS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
The following session settings are available.
•
SESSION LOCKOUT
: This setting specifies the number of failed authentications (the default is three and the maxi-
mum is 99) before the device blocks subsequent authentication attempts for the lockout period. A value of zero means
lockout is disabled.
•
SESSION LOCKOUT PERIOD
: This setting specifies the period of time in minutes of a lockout period (the default is
three and the maximum is 9999). A value of 0 means that there is no lockout period.
e) RESTORE DEFAULTS
PATH: SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
•
LOAD FACTORY DEFAULTS
: This setting is used to reset all the settings, communication and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
f) SUPERVISORY
PATH: SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
MESSAGE
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
SUPERVISORY
LOCAL
AUTHENTICATION:Yes
Range: Yes, No
MESSAGE
Bypass Access:
Disable
Range: Enable, Disable
MESSAGE
LOCK RELAY:
Disable
Range: Enable, Disable
MESSAGE
FACTORY SERVICE:
MODE: Disable
Range: Enable, Disable
MESSAGE
SELF TESTS
See below
MESSAGE
SUPERVISOR ROLE:
Disable
Range: Enable, Disable
MESSAGE
SERIAL INACTIVITY
TIMEOUT: 3
Range: 1 to 9999 minutes
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...