6-6
B90 Low Impedance Bus Differential System
GE Multilin
6.2 STATUS
6 ACTUAL VALUES
6
6.2.9 ETHERNET
PATH: ACTUAL VALUES
STATUS
ETHERNET
These values indicate the status of the primary and secondary Ethernet links.
6.2.10 REAL TIME CLOCK SYNCHRONIZING
PATH: ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
The RTC Sync Source actual value is the time synchronizing source the relay is using at present. Possible sources are:
Port 1 PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, SNTP, and None.
The Grandmaster ID is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable clocks.
Accuracy is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal, how long the relay has had to lock to the time source, and in the case of time signal interruptions, the
length of the interruption. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more,
or that the error cannot be estimated.
PORT 1…3 PTP
STATE
is the present state of the port’s PTP clock. The PTP clock state is:
•
DISABLED
is the port’s function setting is Disabled,
•
NO SIGNAL
if enabled but no signal from an active master has been found and selected,
•
CALIBRATING
if an active master has been selected but lock is not at present established,
•
SYNCH’D (NO PDELAY)
if the port is synchronized, but the peer delay mechanism is non-operational, and
•
SYNCHRONIZED
if synchronized.
ETHERNET
ETHERNET PRI LINK
STATUS: Fail
Range: Fail, OK
MESSAGE
ETHERNET SEC LINK
STATUS: Fail
Range: Fail, OK
MESSAGE
ETHERNET TRD LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC Sync Source:
None
Range: See text below
MESSAGE
GrandMaster ID:
0X0000000000000000
Range: Any 8 octet value
MESSAGE
Accuracy:
999,999,999 ns
Range: 0 to 999, 999, 999 ns
MESSAGE
Port 1 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d,
Synchronized
MESSAGE
Port 2 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d,
Synchronized
MESSAGE
Port 3 PTP State:
NO SIGNAL
Range: Disabled, No Signal, Calibrating, Synch’d,
Synchronized
MESSAGE
PTP - IRIG-B Delta:
999,999,999 ns
Range: -500,000,000 to +500,000,000 ns or
999,999,999 ns
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...