5-46
B90 Low Impedance Bus Differential System
GE Multilin
5.2 PRODUCT SETUP
5 SETTINGS
5
b) DIGITAL CHANNELS
PATH: SETTINGS
PRODUCT SETUP
OSCILLOGRAPHY
DIGITAL CHANNELS
A
DIGITAL 1(63) CHANNEL
setting selects the FlexLogic operand state recorded in an oscillography trace. The length of each
oscillography trace depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. Upon
startup, the relay will automatically prepare the parameter list.
c) ANALOG CHANNELS
PATH: SETTINGS
PRODUCT SETUP
OSCILLOGRAPHY
ANALOG CHANNELS
These settings select the metering actual value recorded in an oscillography trace. The length of each oscillography trace
depends in part on the number of parameters selected here. Parameters set to “Off” are ignored. The parameters available
in a given relay are dependent on:
•
The type of relay,
•
The type and number of CT/VT hardware modules installed, and
•
The type and number of analog input hardware modules installed.
Upon startup, the relay will automatically prepare the parameter list. A list of all possible analog metering actual value
parameters is presented in Appendix A:
FlexAnalog parameters
. The parameter index number shown in any of the tables is
used to expedite the selection of the parameter on the relay display. It can be quite time-consuming to scan through the list
of parameters via the relay keypad and display - entering this number via the relay keypad will cause the corresponding
parameter to be displayed.
If there are no CT/VT modules and analog input modules, no analog traces will appear in the file; only the digital traces will
appear.
DIGITAL CHANNELS
DIGITAL CHANNEL 1:
Off
Range: FlexLogic operand
MESSAGE
DIGITAL CHANNEL 2:
Off
Range: FlexLogic operand
MESSAGE
DIGITAL CHANNEL 3:
Off
Range: FlexLogic operand
MESSAGE
DIGITAL CHANNEL 63:
Off
Range: FlexLogic operand
ANALOG CHANNELS
ANALOG CHANNEL 1:
Off
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
MESSAGE
ANALOG CHANNEL 2:
Off
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
MESSAGE
ANALOG CHANNEL 3:
Off
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
MESSAGE
ANALOG CHANNEL 16:
Off
Range: Off, any FlexAnalog parameter
See Appendix A for complete list.
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...