GE Multilin
B90 Low Impedance Bus Differential System
B-29
APPENDIX B
B.4 MEMORY MAPPING
B
Instantaneous Overcurrent (Read/Write Grouped Setting) (24 modules)
7600
Instantaneous Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7601
Instantaneous Overcurrent 1 CT
0 to 23
---
1
F400
0
7602
Instantaneous Overcurrent 1 Pickup
0.001 to 30
pu
0.001
F001
1200
7603
Instantaneous Overcurrent 1 Pickup Delay
0 to 65.535
s
0.001
F001
0
7604
Instantaneous Overcurrent 1 Reset Delay
0 to 65.535
s
0.001
F001
0
7605
Instantaneous Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
7607
Instantaneous Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7608
Instantaneous Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
7609
Reserved (2 items)
0 to 65535
---
1
F001
0
760A
...Repeated for Instantaneous Overcurrent 2
760B
...Repeated for Instantaneous Overcurrent 3
760C
...Repeated for Instantaneous Overcurrent 4
760E
...Repeated for Instantaneous Overcurrent 5
760F
...Repeated for Instantaneous Overcurrent 6
7612
...Repeated for Instantaneous Overcurrent 7
7614
...Repeated for Instantaneous Overcurrent 8
7615
...Repeated for Instantaneous Overcurrent 9
7618
...Repeated for Instantaneous Overcurrent 10
7619
...Repeated for Instantaneous Overcurrent 11
761C
...Repeated for Instantaneous Overcurrent 12
761E
...Repeated for Instantaneous Overcurrent 13
761F
...Repeated for Instantaneous Overcurrent 14
7622
...Repeated for Instantaneous Overcurrent 15
7623
...Repeated for Instantaneous Overcurrent 16
7626
...Repeated for Instantaneous Overcurrent 17
7628
...Repeated for Instantaneous Overcurrent 18
7629
...Repeated for Instantaneous Overcurrent 19
762C
...Repeated for Instantaneous Overcurrent 20
762F
...Repeated for Instantaneous Overcurrent 21
7631
...Repeated for Instantaneous Overcurrent 22
7632
...Repeated for Instantaneous Overcurrent 23
7633
...Repeated for Instantaneous Overcurrent 24
Time Overcurrent (Read/Write Grouped Setting) (24 modules)
7700
Time Overcurrent 1 Function
0 to 1
---
1
F102
0 (Disabled)
7701
Time Overcurrent 1 CT Setting
0 to 23
---
1
F400
0
7702
Time Overcurrent 1 Pickup
0.001 to 30
pu
0.001
F001
1200
7703
Time Overcurrent 1 Curve
0 to 16
---
1
F103
0 (IEEE Mod Inv)
7704
Time Overcurrent 1 Multiplier
0 to 600
---
0.01
F001
100
7705
Time Overcurrent 1 Reset
0 to 1
---
1
F104
0 (Instantaneous)
7706
Time Overcurrent 1 Block
0 to 4294967295
---
1
F300
0
7708
Time Overcurrent 1 Target
0 to 2
---
1
F109
0 (Self-reset)
7709
Time Overcurrent 1 Events
0 to 1
---
1
F102
0 (Disabled)
770A
Reserved (3 items)
0 to 65535
---
1
F001
0
770C
...Repeated for Time Overcurrent 2
770D
...Repeated for Time Overcurrent 3
7710
...Repeated for Time Overcurrent 4
7712
...Repeated for Time Overcurrent 5
7714
...Repeated for Time Overcurrent 6
7716
...Repeated for Time Overcurrent 7
7718
...Repeated for Time Overcurrent 8
771A
...Repeated for Time Overcurrent 9
771B
...Repeated for Time Overcurrent 10
771D
...Repeated for Time Overcurrent 11
Table B–9: MODBUS MEMORY MAP (Sheet 22 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...