GE Multilin
B90 Low Impedance Bus Differential System
5-93
5 SETTINGS
5.5 GROUPED ELEMENTS
5
5.5GROUPED ELEMENTS
5.5.1 OVERVIEW
Each protection element can be assigned up to six different sets of settings according to setting group designations 1 to 6.
The performance of these elements is defined by the active setting group at a given time. Multiple setting groups allow the
user to conveniently change protection settings for different operating situations (for example, altered power system config-
uration, season of the year, etc.). The active setting group can be preset or selected via the
SETTING GROUPS
menu (see the
Control elements
section later in this chapter). See also the
Introduction to elements
section at the beginning of this chap-
ter.
5.5.2 SETTING GROUP
PATH: SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
Each of the six setting group menus is identical. Setting group 1 (the default active group) automatically becomes active if
no other group is active (see Section 5.6.3: Setting Groups on page 5–119 for further details).
SETTING GROUP 1
BUS DIFFERENTIAL
See below.
MESSAGE
BREAKER FAILURE
MESSAGE
VOLTAGE ELEMENTS
MESSAGE
CURRENT ELEMENTS
MESSAGE
END FAULT PROTECTION
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...