B
6B38
...Repeated for Undervoltage 7
6B44
...Repeated for Undervoltage 8
6B50
...Repeated for Undervoltage 9
6B5C
...Repeated for Undervoltage 10
6B68
...Repeated for Undervoltage 11
6B74
...Repeated for Undervoltage 12
End of Fault Protection (Read/Write Grouped Setting) (24 modules)
6B80
End of Fault Protection 1 Function
0 to 1
---
1
F102
0 (Disabled)
6B81
End of Fault Protection 1 CT
0 to 23
---
1
F400
0
6B82
End of Fault Protection 1 Pickup
0 to 30
pu
0.001
F001
1200
6B83
End of Fault Protection 1 Breaker Open
0 to 4294967295
---
1
F300
0
6B85
End of Fault Protection 1 Breaker Delay
0 to 65.535
s
0.001
F001
400
6B86
End of Fault Protection 1 Manual Close
0 to 4294967295
---
1
F300
0
6B88
End of Fault Protection 1 Pickup Delay
0 to 65.535
s
0.001
F001
40
6B89
End of Fault Protection 1 Block
0 to 4294967295
---
1
F300
0
6B8B
End of Fault Protection 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6BBC
End of Fault Protection 1 Events
0 to 1
---
1
F102
0 (Disabled)
6B8D
...Repeated for End of Fault Protection 2
6B9A
...Repeated for End of Fault Protection 3
6BA7
...Repeated for End of Fault Protection 4
6BB4
...Repeated for End of Fault Protection 5
6BC1
...Repeated for End of Fault Protection 6
6BCE
...Repeated for End of Fault Protection 7
6BDB
...Repeated for End of Fault Protection 8
6BE8
...Repeated for End of Fault Protection 9
6BF5
...Repeated for End of Fault Protection 10
6C02
...Repeated for End of Fault Protection 11
6C0F
...Repeated for End of Fault Protection 12
6C1C
...Repeated for End of Fault Protection 13
6C29
...Repeated for End of Fault Protection 14
6C36
...Repeated for End of Fault Protection 15
6C43
...Repeated for End of Fault Protection 16
6C50
...Repeated for End of Fault Protection 17
6C5D
...Repeated for End of Fault Protection 18
6C6A
...Repeated for End of Fault Protection 19
6C77
...Repeated for End of Fault Protection 20
6C84
...Repeated for End of Fault Protection 21
6C91
...Repeated for End of Fault Protection 22
6C9E
...Repeated for End of Fault Protection 23
6CAB
...Repeated for End of Fault Protection 24
Bus Replica Isolator (Read/Write Setting) (48 modules)
6CBC
Isolator 1 Function
0 to 1
---
1
F102
0 (Disabled)
6CBD
Isolator 1 Open
0 to 4294967295
---
1
F300
0
6CBF
Isolator 1 Closed
0 to 4294967295
---
1
F300
0
6CC1
Isolator 1 Alarm Delay
0 to 120
s
0.05
F001
5
6CC2
Isolator 1 Reset
0 to 4294967295
---
1
F300
0
6CC4
Isolator 1 Target
0 to 2
---
1
F109
0 (Self-reset)
6CC5
Isolator 1 Events
0 to 1
---
1
F102
0 (Disabled)
6CC6
Isolator 1 Reserved (3 items)
---
---
---
F001
0
6CC8
...Repeated for Isolator 2
6CD4
...Repeated for Isolator 3
6CE0
...Repeated for Isolator 4
6CEC
...Repeated for Isolator 5
6CF8
...Repeated for Isolator 6
Table B–9: MODBUS MEMORY MAP (Sheet 15 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...