5-136
B90 Low Impedance Bus Differential System
GE Multilin
5.7 INPUTS/OUTPUTS
5 SETTINGS
5
b) USERST BIT PAIRS
PATH: SETTINGS
INPUTS/OUTPUTS
REMOTE OUTPUTS UserSt BIT PAIRS
REMOTE OUTPUTS UserSt- 1(32) BIT PAIR
Remote outputs 1 to 32 originate as GSSE/GOOSE messages to be transmitted to remote devices. Each digital point in the
message must be programmed to carry the state of a specific FlexLogic operand. The setting above is used to select the
operand which represents a specific UserSt function (as selected by the user) to be transmitted.
The following setting represents the time between sending GSSE/GOOSE messages when there has been no change of
state of any selected digital point. This setting is located in the
PRODUCT SETUP
COMMUNICATIONS
IEC 61850 PROTO-
COL
GSSE/GOOSE CONFIGURATION
settings menu.
For more information on GSSE/GOOSE messaging, refer to Remote Inputs/Outputs Overview in the Remote
Devices section.
5.7.9 RESETTING
PATH: SETTINGS
INPUTS/OUTPUTS
RESETTING
Some events can be programmed to latch the faceplate LED event indicators and the target message on the display. Once
set, the latching mechanism will hold all of the latched indicators or messages in the set state after the initiating condition
has cleared until a RESET command is received to return these latches (not including FlexLogic latches) to the reset state.
The RESET command can be sent from the faceplate Reset button, a remote device via a communications channel, or any
programmed operand.
When the RESET command is received by the relay, two FlexLogic operands are created. These operands, which are
stored as events, reset the latches if the initiating condition has cleared. The three sources of RESET commands each cre-
ate the
RESET OP
FlexLogic operand. Each individual source of a RESET command also creates its individual operand
RESET OP (PUSHBUTTON)
,
RESET OP (COMMS)
or
RESET OP (OPERAND)
to identify the source of the command. The setting
shown above selects the operand that will create the
RESET OP (OPERAND)
operand.
5.7.10 DIRECT INPUTS AND OUTPUTS
a) DIRECT INPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
DIRECT INPUTS
DIRECT INPUT 1(96)
REMOTE OUTPUTS
UserSt- 1 BIT PAIR
UserSt- 1 OPERAND:
Off
Range: FlexLogic operand
MESSAGE
UserSt- 1 EVENTS:
Disabled
Range: Disabled, Enabled
DEFAULT GSSE/GOOSE
UPDATE TIME: 60 s
Range: 1 to 60 s in steps of 1
RESETTING
RESET OPERAND:
Off
Range: FlexLogic operand
DIRECT INPUT 1
DIRECT INPUT 1
NAME: Dir Ip 1
Range: up to 12 alphanumeric characters
MESSAGE
DIRECT INPUT 1
DEVICE ID: 1
Range: 1 to 16
MESSAGE
DIRECT INPUT 1
BIT NUMBER: 1
Range: 1 to 96
MESSAGE
DIRECT INPUT 1
DEFAULT STATE: Off
Range: On, Off, Latest/On, Latest/Off
MESSAGE
DIRECT INPUT 1
EVENTS: Disabled
Range: Enabled, Disabled
NOTE
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...