B-10
B90 Low Impedance Bus Differential System
GE Multilin
B.4 MEMORY MAPPING
APPENDIX B
B
Element Targets (Read Only)
14E3
Target Message
---
---
---
F200
“.”
Digital Input/Output States (Read Only)
1500
Contact Input States (6 items)
0 to 65535
---
1
F500
0
1508
Virtual Input States (8 items)
0 to 65535
---
1
F500
0
1510
Contact Output States (4 items)
0 to 65535
---
1
F500
0
1518
Contact Output Current States (4 items)
0 to 65535
---
1
F500
0
1520
Contact Output Voltage States (4 items)
0 to 65535
---
1
F500
0
1528
Virtual Output States (6 items)
0 to 65535
---
1
F500
0
1530
Contact Output Detectors (4 items)
0 to 65535
---
1
F500
0
Remote Input/Output States (Read Only)
1540
Remote Device States (2 items)
0 to 65535
---
1
F500
0
1542
Remote Input States (4 items)
0 to 65535
---
1
F500
0
1550
Remote Devices Online
0 to 1
---
1
F126
0 (No)
1551
Remote Double-Point Status Input 1 State
0 to 3
---
1
F605
3 (Bad)
1552
Remote Double-Point Status Input 2 State
0 to 3
---
1
F605
3 (Bad)
1553
Remote Double-Point Status Input 3 State
0 to 3
---
1
F605
3 (Bad)
1554
Remote Double-Point Status Input 4 State
0 to 3
---
1
F605
3 (Bad)
1555
Remote Double-Point Status Input 5 State
0 to 3
---
1
F605
3 (Bad)
Platform Direct Input/Output States (Read Only)
15C0
Direct input states (6 items)
0 to 65535
---
1
F500
0
15C8
Direct outputs average message return time 1
0 to 65535
ms
1
F001
0
15C9
Direct outputs average message return time 2
0 to 65535
ms
1
F001
0
15CA
Direct inputs/outputs unreturned message count - Ch. 1
0 to 65535
---
1
F001
0
15CB
Direct inputs/outputs unreturned message count - Ch. 2
0 to 65535
---
1
F001
0
15D0
Direct device states
0 to 65535
---
1
F500
0
15D1
Reserved
0 to 65535
---
1
F001
0
15D2
Direct inputs/outputs CRC fail count 1
0 to 65535
---
1
F001
0
15D3
Direct inputs/outputs CRC fail count 2
0 to 65535
---
1
F001
0
Ethernet Fibre Channel Status (Read/Write)
1610
Ethernet primary fibre channel status
0 to 2
---
1
F134
0 (Fail)
1611
Ethernet secondary fibre channel status
0 to 2
---
1
F134
0 (Fail)
1612
Ethernet tertiary fibre channel status
0 to 2
---
1
F134
0 (Fail)
Bus Differential Actual Values (Read Only) (4 modules)
21D0
Bus zone 1 differential magnitude
0 to 999999.999
A
0.001
F060
0
21D4
Bus zone 1 differential angle
-359.9 to 0
degrees
0.1
F002
0
21D5
Bus zone 1 restraint magnitude
0 to 999999.999
A
0.001
F060
0
21D7
Bus zone 1 restraint angle
-359.9 to 0
degrees
0.1
F002
0
21D8
Bus zone 1 maximum CT
0 to 50000
---
1
F060
1
21DA
Reserved (4 items)
---
---
---
F001
0
21DE
...Repeated for bus zone 2
21EC
...Repeated for bus zone 3
21FA
...Repeated for bus zone 4
Bus Actuals (Read Only) (4 modules)
21E2
Breaker 1 Arcing Current Phase A
0 to 99999999
kA
2
-cyc
1
F060
0
Bus Actuals (Read Only) (4 modules)
21E5
...Repeated for module number 2
Bus Actuals (Read Only) (4 modules)
21E8
...Repeated for module number 2
Bus Actuals (Read Only) (4 modules)
21EC
...Repeated for module number 3
Bus Actuals (Read Only) (4 modules)
21F0
...Repeated for module number 3
Table B–9: MODBUS MEMORY MAP (Sheet 3 of 48)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...