GE Multilin
B90 Low Impedance Bus Differential System
5-57
5 SETTINGS
5.2 PRODUCT SETUP
5
Figure 5–13: USER-PROGRAMMABLE PUSHBUTTON LOGIC (Sheet 2 of 2)
User-programmable pushbuttons require a type HP or HQ faceplate. If an HP or HQ type faceplate was ordered
separately, the relay order code must be changed to indicate the correct faceplate option. This can be done via
EnerVista UR Setup with the
Maintenance > Enable Pushbutton
command.
5.2.15 FLEX STATE PARAMETERS
PATH: SETTINGS
PRODUCT SETUP
FLEX STATE PARAMETERS
FLEX STATE
PARAMETERS
PARAMETER 1:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 2:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 3:
Off
Range: FlexLogic operand
MESSAGE
PARAMETER 256:
Off
Range: FlexLogic operand
Pushbutton 1
LED
Instantaneous
reset *
OR
1. If pushbutton 1 LED control is set to off.
2. If pushbutton 1 LED control is not set to off.
PUSHBUTTON 1 LED LOGIC
OR
AND
AND
SETTING
= Disabled
= High Priority
Message Priority
= Normal
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
Pushbutton 1
LED
SETTING
= any FlexLogic operand
PUSHBTN 1 LED CTL
AND
SETTING
Flash Message Time
T
RST
0
PUSHBUTTON ON
LATCHED
LATCHED/SELF-RESET
AND
From user-programmable
pushbuttons logic
sheet 1, 842021A3
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
FLEXLOGIC OPERAND
PUSHBUTTON 1 OFF
SETTING
T
RST
0
Instantaneous
reset *
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
= XXXXXXXXXX
Top Text
= XXXXXXXXXX
On Text
The message is temporarily removed if
any keypad button is pressed. Ten (10)
seconds of keypad inactivity restores
the message.
LCD MESSAGE
ENGAGE MESSAGE
SETTINGS
= XXXXXXXXXX
Top Text
= XXXXXXXXXX
On Text
Instantaneous reset will be executed if any
front panel button is pressed or any new
target or message becomes active.
842024A2.CDR
OR
FLEXLOGIC OPERAND
PUSHBUTTON 1 ON
PUSHBUTTON 2 ON
PUSHBUTTON 3 ON
PUSHBUTTON 16 ON
FLEXLOGIC OPERAND
ANY PB ON
The enhanced front panel has 16 operands;
the standard front panel has 12
Flash Message Time
NOTE
Содержание B90 UR Series
Страница 28: ...1 20 B90 Low Impedance Bus Differential System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 114: ...4 28 B90 Low Impedance Bus Differential System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 272: ...6 14 B90 Low Impedance Bus Differential System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 316: ...A 4 B90 Low Impedance Bus Differential System GE Multilin A 1 PARAMETER LISTS APPENDIX A A ...
Страница 406: ...B 90 B90 Low Impedance Bus Differential System GE Multilin B 4 MEMORY MAPPING APPENDIX B B ...
Страница 436: ...C 30 B90 Low Impedance Bus Differential System GE Multilin C 7 LOGICAL NODES APPENDIX C C ...
Страница 446: ...D 10 B90 Low Impedance Bus Differential System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...