MDE-4334C Atlas Start-up and Service Manual · April 2008
Page 5-29
Programming 8700 Series Units
Pump Programming
Programming 8700 Series Units
General Programming Details
The mechanical computer can be set for the price range and PPU (gallon/liter) dispensed.
Adjustments for volume of the product dispensed is accomplished at the meter calibration
adjustment wheel.
Note: 9100 Series units do not require programming.
Figure 5-10: Variator Assembly for Mechanical Units
Totalizers
Dollars/Cents
Gallons/Liters
PPU
Note: The unit shown to the left
is an example of a one
type of Totalizer. The
example shown is a
Mechanical Totalizer and
as such is used only in
mechanical units.
Curved Panel Ends
Programming Steps
Setting Calibration
Gasboy Atlas pumps and dispensers are adjusted for accurate measure at the factory. It is the
responsibility of the installer to check the unit for accuracy and make the necessary
adjustments. Where required, it is the owner’s responsibility to report this device to the local
Weights and Measures authority for inspection before putting the unit in service. For setting
the calibration refer to
Setting Prices
To set the prices, proceed as follows:
1
Unlock and remove the front panel. Repeat this procedure for the other side.
2
The variator section of the computer register(s) is exposed to allow for price changes. Slide the
variator cover of the computer register apart to expose the price range arms.
3
There are three range arms located in the variator section. One sets the tenths of a cent
position, one sets the one cent position, and the last one sets the ten cents position. To change
a setting, grasp a range arm and raise it to clear the range arm locator, and relocate the range
arm to the desired setting. Ensure that the range arm is totally bottomed on its setting. Repeat
this for all range arm settings, if necessary.