MDE-4334C Atlas Start-up and Service Manual · April 2008
Page 3-3
Start-up Checklists
Start-up Procedures
Electrical Related Items Checklist
Item
Procedure
See
Checked
1
Equipment must be installed in conjunction with an emergency power
cut-off to shut off all power from the equipment in case of an
emergency.
• MDE-4333 Site
Prep Manual
• FE-356, 357
Field Wiring
Diagram
2
STP isolation relays are required for all dispensers.
3
(Retail 8800 Only): Use twisted pair wires as specified for 2-wire
communication for new installations or where new wire is pulled. Do
not use a shielded wire.
4
All wiring must be stranded copper of the gauge and insulation casing
specified.
5
All grounds must be properly connected as per the installation manual
requirements as well as state, local, and national codes.
MDE-4331
Installation
Manual
6
Conduit should be approved for hazardous locations and properly
sized for the wiring involved.
• NFPA 30A
• NFPA 70
• UL 87
• NEC
7
Properly size all circuit breakers for the units/unit options involved.
NEC and local
codes
8
All dispenser/pump wiring should be properly spaced and isolated from
wiring for electrically noisy devices such as variable speed STPs,
station equipment motors, and other devices.
MDE-4333 Site
Prep Manual
9
All power wiring and circuit breakers to Gasboy Atlas equipment must
be dedicated and not be shared with other equipment.
10
All circuit breakers to Gasboy Atlas equipment must be clearly labeled
and readily accessible.
11
All Distribution Boxes (D-Box) must be clearly labeled showing the
dispenser/pump number connections.
12
All dispensers/pumps must be wired to the same phase of electrical
power.
13
New site wiring must be Megger tested. Old site wiring must be
continuity and short-tested with a digital meter.
14
Wiring color must be coded or tagged, sized for distance and
application, and resistant to gas and oil.
15
Remove all tie wraps securing pulsers and ensure that the pulser is
able to float (Pumps).
16
Confirm proper wiring, if used with a Gasboy FMS (using the
appropriate FMS installation manual). The manuals to be referred to
are:
• C35963 CFN Islander Installation Manual
• MDE-4298 CFN 3 Installation Manual
• MDE-4319 TopKAT Installation Manual
• Series 1K Installation Manual