MDE-4334C Atlas Start-up and Service Manual · April 2008
Page 4-9
Preventive Maintenance Table
Preventive Maintenance and Inspection
Leaks, external
(continued)
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or
death.
Do
not
attempt to service the Gasboy Atlas pump/dispenser yourself, and do
not
allow untrained personnel to service Gasboy Atlas pumps/dispensers.
Only Gasboy Atlas-trained ASCs should service a Gasboy Atlas unit.
Displays
(Electronic units)
Once a week
1
Inspect displays for proper reading of all digits.
2
Verify if the displays are properly backlit.
• Owner—
Inspect
• ASC only—
Repair and test
Breakaways
Once a week or after
drive-offs
1
Inspect breakaways for secure connections to the hose and for any
leaks.
2
For units with hose retrievers, position the breakaway coupling
between the retriever connection to the hose and the nozzle. The
breakaway whip hose should be attached to the nozzle.
3
Consult the breakaway manufacturer for any additional required
inspections.
4
If repair is needed, call an ASC to make the repairs.
WARNING
Leaking fuel can be ignited, causing a fire or explosion.
Fire, explosion, or electrical shock could result in severe injury or death if
you continue to use damaged pumps/dispensers.
If you find any leaks or damage, stop using the pump/dispenser, and contact
your local ASC.
WARNING
The pump/dispenser contains pressurized flammable fuel and lethal
voltages.
Servicing a Gasboy Atlas unit incorrectly could result in severe injury or
death.
Do
not
attempt to service the Gasboy Atlas pump/dispenser yourself, and
do
not
allow untrained personnel to service Gasboy Atlas pumps/
dispensers. Only Gasboy Atlas-trained ASCs should service a Gasboy
Atlas unit.
• Owner—
Inspect
• ASC only—
Repair and test
Warning tags
and operating
instructions
Once a week
Inspect for and replace all missing, damaged, or unreadable warning tags
or operating instructions.
• Owner—
Inspect
• Owner or
ASC—Replace
Components
Recommended
Frequency
Recommended Maintenance
Who Performs the
Inspection/Repair