MDE-4334C Atlas Start-up and Service Manual · April 2008
Page 5-23
Programming 8800 Series Units
Pump Programming
Function Code 17: Stop Control
Turns off one or both sides of the unit if the
Stop
option is pressed.
0 = Stop controls one side
1 = Stop controls two sides
Function Code 18: Zero Previous Transaction After Pump Handle Operation
Resets the last transaction after the pump handle is raised and the unit is authorized (required
for New Jersey, US).
0 = Zero after lamp test
1 = Zero before lamp test (Required for New Jersey)
Function Code 19: Lamp Test (Leak Detector Test)
It is not actually a lamp test; but it programs the amount of time the dispenser valves take to
open, after the handle is raised. Primarily used for dispensers with mechanical STP leak
detectors to allow the leak detector enough time to run its test.
1 = 1 second
2 = 2 seconds
3 = 3 seconds
4 = 4 seconds
5 = 5 seconds
6 = 6 seconds
7 = 7 seconds
8 = 8 seconds
9 = 9 seconds
Function Code 20: Programmable Pump Preset Value
Set to
1
for use with six-digit cash programming.
0 = Value X 1
1 = Value X 10
Function Code 21: PPU Blinking Option
0 = No PPU Blinking
1 = PPU Blinking
Function Code 22: Volume Decimal Point
0 = xxx.xxx
1 = xxxx. xx (export only)
Function Code 23: Program STP Control
0 = Off
1 = On
Command Code 11: Grade Assignment (perform this at console)
Assigning Grades. Normally not used, as grades should be programmed using the POS.
Command Code 12: Pump Program
This is also a multi-purpose code with sub-codes. Not all codes are used for the Atlas. If
accessible, do not change other codes from their default value or the pump/dispenser may not
work properly.