6-72
(2) Torque command monitor
Monitor the torque command value from MICREX.
(Condition: T-Link station address: 24, 8+8 words)
WB38
1 0 0 0
Torque command value monitor (link No. 10h)
39
0 0 0 0
↓
After read completes
WB24
1 0 0 0
When the link number requesting polling is returned to this area, reading
is completed.
25
0 0 0 0
Torque command value monitor data
26
1 3 8 8
1388 (h) × 100 (%) / 10000
=
50 (%)
27
0 0 0 0
28
0 0 0 0
↓
29
0 0 0 0
From the above, the torque command value is "50% of drive".
(3) Function code data setting
Set the function code S08 "Acceleration time" to 30.5 seconds from MICREX.
(Condition: T-Link station address: 58, 4+4 words)
WB62
0 0 0 0
Function code S08 selecting (Link No. 08h)
63
0 0 0 0
131
(h)
=
305,305×0.1s
=
30.5s
64
0 8 0 8
65
0 1 3 1
Poll the function code S08 to confirm setting completion.
↓
After writing
completes
WB58
* *
* *
Poll the function code S08.
59
* *
* *
131
(h)
=
305,305×0.1s
=
30.5s
60
0 8 0 0
(Data is correctly set.)
61
0 1 3 1
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...