Operation Function Codes
This section describes operation to be performed when communications link errors occur in a state, where
running command or speed command is given via CC-Link, while the inverter is running.
(1) Function code o30 = 0, o31 = 5.00 (Communication error continues for 5 or more seconds, and the
motor coasts to stop)
Figure 6.7.9
(2) Function code o30 = 0, o31 = 5.00 (Communication error continues for 5 or more seconds, and the
motor decelerates to stop)
Figure 6.7.10
*1) For the period until the recovery of communications, the command just before the occurrence of the communications error (run
command and/or speed command) is retained.
*2) During DC braking [DCBRK] or pre-exciting [EXITE] in deceleration to stop, alarm relay output is not performed until the
stop of these commands.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...