6.7 CC-Link Interface Card
6-173
Chap. 6
CO
NTR
O
L O
P
TIONS
6.7.9
1 X mode with 1 station occupied (o32=0
)
6.7.9.1
Remote I/O signal in 1 X mode (o32=1)
Table 6.7.20 Remote Output (Master -> FRENIC-VG)
Device No.
Signal name
Description
RYn0
Run forward command
OFF: Stop command
ON: Run forward command (counterclockwise viewed from
the motor axis direction)
RYn1
Run reverse command
OFF: Stop command
ON: Run reverse command (counterclockwise viewed from
the motor axis direction)
Simultaneously turning
RYn0 and RYn1 ON is
functionally equivalent
to a stop command.
RYn2
Terminal X1 function
RYn3
Terminal X2 function
RYn4
Terminal X3 function
RYn5
Terminal X4 function
Multiple speed (SS1/SS2/SS4/SS8) is selectable by
combinations of terminals.
RYn6
Terminal X5 function
RYn7
Terminal X6 function
ASR and acceleration/deceleration (RT1/RT2) can be
selected by combinations of terminals.
RYn8
Terminal X8 function
Works as error reset (RST) when turned ON.
RYn9
Terminal X7 function
Works as coast to stop command (BX) when turned ON.
(output shut down on the secondary side)
RYnA
Terminal X9 function
External alarm
0h2
is generated when turned ON.
RYnB
Terminal X11 function
Command assigned with inverter function code E10
Functions to be provided
by factory default are
shown at left. Setting
terminal X function can
change the function of
terminal X.
(Function code E01-E10)
RYnC
Monitor command
Turning the monitor command (RYnC) ON specifies a monitored value for monitored
values 1 to 6, turning the "Monitoring" signal (RXnC) ON.
Note 1
RYnD
Speed setting command
(RAM)
Turning the speed setting command (RYnD) ON writes the speed command (RWwn+1)
into the inverter's volatile memory (RAM).
Note 2
Upon completion of writing, the speed setting completed signal (RXnD) is turned ON.
RYnE Not
used.
-
RYnF Command
code
execution request
Turning the command code request signal (RYnF) ON executes processing
corresponding to command codes specified in command codes 1 to 6.
Note 3
After execution of those command codes, the "Command code execution completed"
signal (RXnF) is turned ON. If a command code execution error occurs, the response
code (RWrn+2) is set to a value other than "0".
RY(n+1)0
|
RY(n+1)3
Not used.
Should be turned OFF.
RY(n+1)4 Terminal X12 function
Command assigned with inverter function code E11
RY(n+1)5 Terminal X13 function
Command assigned with inverter function code E12
RY(n+1)6 Terminal X14 function
Command assigned with inverter function code E13
RY(n+1)7
|
RY(n+1)9
Not used.
Should be turned OFF.
RY(n+1)A Alarm
reset
request flag
When an inverter alarm is generated, turning the alarm reset request flag ON resets the
inverter, turning the alarm status flag (RX(n+1)A) OFF.
Note 4
RY(n+1)B
|
RY(n+1)F
Not used.
Should be turned OFF.
n: Value determined by a station address
Note 1: While the "Monitor command" (RYnC) is ON, the monitored values are constantly updated.
Note 2: While the "Speed setting" (RYnD) is ON, the value of speed command (RWwn+1) is constantly reflected on the speed.
Note 3: When the command execution request is switched from OFF to ON, the command code is executed only once.
Note 4: When the "Alarm reset request flag" signal (RY(n+1)A) is ON, alarm reset is constantly executed. After the release of the
alarm, this signal should therefore be turned OFF. Alarm reset can be done regardless of operation mode.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...