Composition of inverter and wire length of motor power line for direct parallel connection for motor capacity are
described below.
However, combination other than as given in the chart may be used for direct parallel connection. Please feel
free to contact us.
6.6.12.1 Wiring
length
in MD specification
Table 6.6.22 Rating in Direct Parallel Connection
(MD Specification)
Motor specification
Rating specification in direct parallel connection
Current
specification
Rated
capacity
[kW]
Rating
[A]
Overload
[A]
INV type
FRN
-4
No. of
units
Rated
current
[A]
Wiring
length
[m]
Fig.
355 650
975
200SVG1
x
2
716
14.6
(a)
400 740
1110
220SVG1
789
13.2
500 960
1440
280SVG1
988
12.0
630 1170
1755
220SVG1
x
3
1183
17.6
(b)
710 1370
2055
280SVG1
1482
15.6
800 1480
2220
14.1
1000 1850
2775
630BVG1
x
2
2223
4.7
(c)
1200 2220
3330
1500 2775
4163
800BVG1
2812
4.0
1800 3330
4995
630BVG1
x
3
3335
6.3
(d)
2000 3700
5550
710BVG1
3905
5.3
2400 4218
6327
800BVG1
4218
4.9
6.6.12.2 Wiring
length
in LD specification
Table 6.6.23 Rating in Direct Parallel Connection
(LD Specification)
Motor specification
Rating specification in direct parallel connection
Current
specification
Rated
capacity
[kW]
Rating
[A]
Overload
[A]
INV type
FRN
-4
No. of
units
Rated
current
[A]
Wiring
length
[m]
Fig.
400 740
1110
200SVG1
x
2
789
13.2
(a)
500 960
1440
250SVG1
988
12.0
630 1170
1755
315SVG1
1235
17.6
710 1370
2055
250SVG1
x
3
1482
17.6
(b)
800 1480
2220
250SVG1
15.6
1000 1850
2775
315SVG1 1853
14.1
1200 2220
3330
630BVG1
x
2
2603
4.7
(c)
1500 2775
4163
710BVG1 2812
1800 3330
4995
800BVG1 3515
4.0
2000 3700
5550
630BVG1
x
3
3905
6.3
(d)
2400 4218
6327
710BVG1 4218
5.3
3000 5178
5695
800BVG1 5273
4.9
Figure 6.6.15
Explanation diagram
The electric wire sizes are specified by recommended electric wire sizes (FLSC electric wires) in the
case of atmospheric temperature of 40°C or lower in Chapter 4. When significantly different electric
wire sizes or cabtire cables/shielded wires are used, wiring length should be reconsidered as inductance
of power line change.
In identical power line size in cabtire radio shield wire, a long power line with approximately 3 times
the length shown in the chart should be used.
(a) Stack 2 units
U V W
U V
W
U
V
W
U V W U
V
W
(c) Stack for each phase 2 units
(d) Stack for each phase 3 units
(b) Stack 3 units
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...