![Fuji Electric FRENIC-VG Series Скачать руководство пользователя страница 191](http://html1.mh-extra.com/html/fuji-electric/frenic-vg-series/frenic-vg-series_user-manual_2341868191.webp)
6.5 SX Bus Interface Card
6-115
Chap. 6
CO
NTR
O
L O
P
TIONS
[ 3 ]
Degenerate setting
The SX bus option supports the degenerate and degenerate system start-up operations. Each operation has
restrictions including the degenerated condition and system settings. For the details, refer to the user's
manual (reference) of each MICREX-SX series product.
The following explains the degenerate setting and degenerate system start-up setting. These settings are
not required if the degenerate setting and degenerate system start-up operations are not necessary.
(1) Degenerate
Setting
With the degenerate setting enabled, even when an inverter error occurs and the inverter stops, other
normal module can continue operation.
Open the [CPU Parameter] dialog box, and click the [Degenerate Setting] tab.
Figure 6.5.31
(2) Degenerate System Start-up Setting
With the degenerate system start-up setting enabled, when the SX bus system launches with the
inverter powered off, the system will start up after the configuration check standby time, excluding
the inverter, in a light alarm state.
In the [System Properties] dialog box, click the [Degenerate System Start-up Operation Definition] tab.
Figure 6.5.32
Select the degenerate system start-up operation mode
with the option button, and then select the degenerate
start-up station address from the list box.
Select the inverter from the I/O list and click the
[>>] button to register degenerate setting.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...