6-60
6.4.5 Function
code
• Incorrect function code data may result in a dangerous situation. After setting and writing the data, check it
again.
An accident could occur.
By installing the T-Link interface card, the dedicated function codes of o29 to o32 will be available.
Table 6.4.4
Function code name
No.
Name
Touch panel display
Available
scope
Description
0 Invalid
1
Operation 1
(ON: Continue operation, OFF: Immediately
er4
for heavy alarm)
o29
Operation
continuation
signal operation
upon alarm
LK-D OPE
2
Operation 2 (ON: Continue operation, OFF:
Follow o30 for heavy alarm)
0
Immediately force operation to stop upon
communication error (light alarm) occurrence
(
er4
alarm: coast to stop).
1
After a communication error (light alarm)
occurs, continue operation for the timer time (run
command from the previous communication is
held in the communication error state). Force
operation to stop after the timer time (
er4
alarm: coast to stop).
If the communication recovers during the timer
time, the command received in communication is
run. But, operation is forced to stop it the error
persists after the timer time.
2
After a communication error (light alarm)
occurs, continue operation for the timer time (run
command from the previous communication is
held in the communication error state). Force
operation to stop if the communication error
persists after the timer time.
If the communication recovers during the timer
time, the command received in communication is
run.
o30
Error processing
after detection of
transmission failure
MODE ON ER
3
No alarm (
er4
) even when a communication
error (light alarm) occurs.
The run command from the previous
communication is held in the communication
error state.
If the communication recovers, the command
received in communication is run.
o31
Operation time
after detection of
transmission failure
TIMER TL
0.01 to
20.00s
Operation time timer value [s] for a
communication error (light alarm) is effective
when o30=1 or 2.
0, 1
0: Format 1
(Standard format 4 W + 4 W)
1: Format 2
(FRENIC-VG format 8 W + 8 W)
o32
Transmission format
selection
4W/8W
SEL
2 to 4
For CC-Link option.
Not used for T-Link option.
Available soon
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...