6.5 SX Bus Interface Card
6-89
Chap. 6
CO
NTR
O
L O
P
TIONS
6.5.6.2 Protective
operation function code
The following explains how to control the
er4
alarm when a light alarm occurs while an operation
command is given from MICREX-SX via the SX bus.
[Operation Description]
The following describes an example of operation when operation and speed commands are given from
MICREX-SX and a communication error occurs during operation.
*1 During this period of time, if communication recovers and new commands or settings are not sent,
commands (for operation or speed, or both) received upon error occurrence are held.
(1) When function code o30 = 0
Figure 6.5.12
(2) When function code o30 = 1 and o31 = 5.0 (when a communication error occurs, the motor coasts to
stop in five seconds.)
Figure 6.5.13
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...