6.7 CC-Link Interface Card
6-165
Chap. 6
CO
NTR
O
L O
P
TIONS
(3) Function code o30 = 2, o31 = 5.00 (Communication error continues for 5 or more seconds, and the
motor decelerates to stop)
Figure 6.7.11
(4) Function code o30 = 2, o31 = 5.00 (After communication error continues for 5 or more seconds,
returns to communications during deceleration to stop)
Ordinary
Communications error
Normal
Normal
Communications status
Display
FWD
Speed command
Batch failure
Stopped due to
communications error
*1
[LK-ERR]
[C-D09]
The motor is accelerated to the command speed
even if a transmission error occurs during acceleration.
ON
5.00s
ON
Operation
Stop Operation
Command
from master
FWD
Internal setting
of FRENIC-VG
Reference speed 2
(M50)
Reference speed 3
(M51)
Figure 6.7.12
*1) For the period until the recovery of communications, the command just before the occurrence of the communications error (run
command and/or speed command) is retained.
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...