6.7 CC-Link Interface Card
6-155
Chap. 6
CO
NTR
O
L O
P
TIONS
*1 Number of units connectable
Since the number of stations occupied differs depending on the use of a
different unit (remote I/O station or remote device station) or use of different profiles, both the
formulae must be satisfied.
Formula 1: (1 x a) + (2 x b) + (3 x c) + (4 x d)
≤
64
a:
Number with 1 station occupied, b:
Number with 2 stations occupied, c:
Number with 3
stations occupied, d:
Number with 4 stations occupied
Formula 2: (16 x A) + (54 x B) + (88 x C)
≤
2304
A: Remote I/O station................................................................................ Max. 64 units
B: Remote device station........................................................................... Max. 42 units
C: Local station, standby master station, intelligent device station ........... Max. 26 units
Rotary switch RSW1, 2
Before turning on the power supply to the inverter, specify inverter station addresses
in the range of 1 to 64.
STATION No.
×10
×1
RSW1
RSW2
Figure 6.7.2
Note 1: Do not change station address settings when the
inverter power is ON. If a station address is changed
when the power is ON, the station address after the
change is not available to provide data communications.
Note 2: If a station address is double assigned or is set out of
the allowable range, normal communications cannot be
carried out. (L.ERR LED lights.
)
Note 3: Specify consecutive station addresses in connection
order. (If station addresses are not specified
consecutively, specify a "reserved station address" for
each skipped station address.)
Transmission baud rate setting switch RSW3
Before turning on the power supply to the inverter, specify transmission baud rate in
the range of 0 to 4.
Table 6.7.2 Baud rate specification
Figure 6.7.1
Figure 6.7.3
Number Baud
rate
0 156
Kbps
(
Factory default
)
1 625
Kbps
2 2.5
Mbps
3 5
Mbps
4 10
Mbps
5 - 9
Setting error (L.ERR LED lights)
LED status indicators
The link status of CC-Link can be checked with four LEDs.
B.RATE
RSW3
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...