6-42
6.2.6 Check
functions
6.2.6.1 Optional
equipment
check
You can check on the keypad whether the PG interface expansion card is set to SD, LD, PR, or PD.
From the Operating Mode screen, go to the Program Menu screen
and select "4. I/O check." Use the
and
keys to switch
screens and check the setting on screen 9 as shown in the figure to
the right.
For more information, see the section on keypad operation.
The figure to the right illustrates the screen that would be
displayed when two PG interface expansion cards are installed and
set to PG (PD) and PG (SD).
6.2.6.2 I/O
check
You can check the PG interface expansion card's digital input status on the inverter's keypad.
From the Operating Mode screen, go to the Program Menu screen and select "4. I/O check." Use the
and
keys to switch screens and check the setting on screen 15 as shown in the figure below.
For more information, see the section on keypad operation.
6.2.7 Protective
functionality
When the inverter's protective functionality operates, the inverter immediately displays an alarm, displays
the alarm name on the keypad's LED, and allows the motor to free-run. When this functionality operates,
resume operation after clearing the cause of the malfunction. Avoid automatically resetting the alarm, for
example with an external sequence. Table 6.2.17 lists alarms related to the PG interface expansion card.
For more information about other alarms, see "Protective Operation" in the inverter's operating manual.
Table 6.2.17 List of Alarm Protective Functions
Alarm display
30X
Alarm cause
d0
Operation
This position deviation overrun error occurs when the load causes the motor startup to
lag relative to the pulse train command, creating a position deviation that exceeds a
previously set value. The threshold is set with function code o18 (deviation overrun
width).
p9
Operation
A broken wire was detected due to an interruption in a PG signal when line driver
operation (OPC-VG1-PG) was selected while using the SD setting.
OPTION
OPA:VG1-PG(SD)
OPB:VG1-PG(PD)
OPC:
∧∨
Æ
PAGE
SHIFT
9
Inverter and PG (SD) signal input information
PG (LD) signal input information
PG (PR) signal input information
PG (PD) signal input information
SD =±×××××P/s
LD =±×××××P/s
PR =±×××××P/s
PD =±×××××P/s
∧∨
Æ
PAGE
SHIFT
15
Содержание FRENIC-VG Series
Страница 1: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...
Страница 2: ......
Страница 3: ...High Performance Vector Control Inverter User s Manual Option Edition ...
Страница 155: ...6 5 SX Bus Interface Card 6 79 Chap 6 CONTROL OPTIONS Figure 6 5 5 ...
Страница 156: ...6 80 Basic Connection Diagram Figure 6 5 6 ...
Страница 203: ...6 6 High Speed Serial Communication Capable Terminal Block 6 127 Chap 6 CONTROL OPTIONS Figure 6 6 3 ...
Страница 234: ...6 158 6 7 3 External dimension drawing 17 Unit mm Figure 6 7 5 Option PCB Outline Drawing Tightening torque 0 4 N m ...
Страница 344: ......
Страница 346: ...For the STACK type User s Manual User s Manual Option Edition 24A7 E 0045 3 ...